ADL100 -EY/ADL300-EY Operation Manual of wireless prepaid watt-hour meter Installation and operation instruction V1.0 ACREL Co,.Ltd...
Page 2
Declare The copyright is the property of Acrel. Any information in any paragraph or section cannot be extracted, copied or otherwise reproduced or propagated. Otherwise offenders shall take all consequences. All rights are reserved. Acrel reserves the right to modify the product specifications herein without notification.
Page 3
Record of amendments to specifications The old Date New Edition Modify the content version 2022/4/10 V1.0...
1 General ADL100-EY single phase wireless prepaid watt-hour meter,ADL300-EY three phase wireless prepaid watt-hour meter are used for calculating the single and three phase active energy respectively on the frequency of 50 Hz. The meter has functions of pre-paid, load controlling, time control and NB,2G,4G,Wifi,RS485 communication etc.Products meet the Enterprise Standard Q31/0114000129C039-2019《Enterprise Standard for electronic prepayment watt-hour meter》...
Real time demanded □ □ Historical freeze, power purchases □ □ Date, time,week □ □ Infrared communication □ ■ The second communication path: Communication interface: RS485, ■ ■ Communication protocol: Modbus-RTU 4G Communication □ □ communication Wifi/ Bluetooth Communication □ □...
Page 7
Reference 220V 3×220/380V voltage voltage Consumption <10VA(Single phase) Impedance >2MΩ Accuracy class ±0.2% Error Measurement Input current 10(60)A 3×1(6)A, 3×10(80)A current Consumption <4VA(Single phase rated current) Accuracy class ±0.2% Error Power Active, reactive, apparent power, error±0.5℅ Frequency 45~65Hz,Error±0.2% Active energy Active energy meter- Energy...
Page 9
derect connect connect via CT Note:The torque of direct connect should not be greater than 4.0N·m,and the torque of connect via CT should not be greater than 2.0N·m。...
6 Wiring and installing Wiring sample of voltage and current ADL100-EY ADL300-EY Three phase three lines direct connect ADL300-EY Three phase four lines direct connect 21 22 X1 X2 24 25 40 41 42 43 RS485 有功 2路通讯 跳闸 合闸...
Wiring Diagram of auxiliary function Note: 1. When the instrument band internal control function, (40-41) , (42-43) default can not be used. If need to use, need the customer to indicate in the order form. When tripping, a voltage should be introduced to 40 and 41 connected to the control terminal of the corresponding circuit breaker.
Page 12
7.2 Display the switch operation Three types of view key can be achieved through the screen display. The order of the various display interfaces is illustrated as follows: : Voltage, current, active power, apparent power, frequency, power factor, date, time, address, version number, full display detection :Total power consumption, peak power consumption, average power consumption, valley power consumption, meter number, alarm amount 1, alarm amount 2, current electricity price, times of power purchase, power threshold...
Instrument communication interface support,The baud rate of communication port can be set between 1200BPS, 2400bps, 4800bps, 9600bps, 19200bps and 38400bps,The check bit can be set to no check or even check. 8.1 MODBUS protocol communication address table ADL100-EY communication address table Address Variable...
0001:Pulse output 0064H-035FH Reserved Communication address:1~247 Baud rate:0:1200 Main communication: 1:2400 0360H Communication address and UINT8×2 2:4800 baud rate 3:9600 4:19200 5:38400 Check bit:0:No check 1:Odd check 2:Even check 0361H Check bit stop bit UINT8×2 Stop bit:0:11 stop bit 1:1.51 stop bit 2:21 stop bit 0362H-0364H Reserved...
Page 15
Starting time of the 14th period: minutes Starting time of the 14th period: hour ADL300-EY Read / Starting address Data item name length remarks write 0000H Current total electricity UINT32 Current spike electric 0002H UINT32 energy Calculating factor0.01 0004H Current peak electric energy UINT32 unit:kWh 0006H...
Page 16
004AH Credit amount UINT32 004CH New purchase amount INT32 004EH Times of power purchase UINT16 Range of values(0~9999) 004FH Remaining amount INT32 Calculating factor:0.01 0051H Total purchase amount INT32 Yuan 0053H-0056H Reserved 0001:Override it 0057H Mandatory control word UINT16 0000:Forced shutdown 0000:Forced closing 0058H On off control word...
Page 17
036AH-1FFFH Reserved Schedule 1: Session 1 tariff number Starting Time of session 1: Minutes Rate Number: Starting Time of session 1: 01 for Pointy hours 2000H INT8×42 02 for peaks …… 03 for Ping Section 14 tariff number 04 for Valley Starting Time of session 14: minutes Session 14 starting time:...
Page 18
0x1313 0x1314 0x1315 0x1316 0x1317 0x1318 0x1319 Number of devices 0x131A / number of data segments Number of alarm 0x131B segments / TCP_ UDP mode 0x131C 1Data length 1 0x131D 2Data length 2 0x131E 3Data length 3 0x131F 4Data length 4 0x1320 5Data length 5 0x1321...
Page 19
0x1333 control bit 8 0x1334 Firmware upgrade flag 0x1335 0x1336 Total number of firmware packages 0x1337 ADL100-EY、ADL300-EY Wireless information area 0x1700 Software number Software version 0x1701 number Server connection High 8 BITS: Server Connection 0x1702 status / signal value Status Low 8 BITS: signal value...