SUN2000-(3KTL-10KTL)-M1 Series
User Manual
Parameter
Charge from grid
Grid charge cutoff
SOC
7.2.1.4 Capacity Control
Prerequisites
The screenshots in this section are captured from the SUN2000 app 6.23.00.125.
The actual screens may vary with app updates.
Description
If the inverter connects to an ESS and the ESS working mode is set to Maximum
self-consumption or TOU, you can set capacity control parameters.
Table 7-3 Application Scenario
Applicable Model
SUN2000-(3KTL-10K
TL)-M1 series
Parameter Settings
On the home screen, choose Power adjustment > Capacity control and set
capacity control parameters.
Issue 17 (2024-01-12)
NO TE
● The capacity control function is unavailable when the energy storage working mode is
set to Fully fed to grid.
● When capacity control has been enabled, you must first disable capacity control and
then set the energy storage working mode to Fully fed to grid.
Copyright © Huawei Technologies Co., Ltd.
Description
If Charge from grid function is
disabled by default, comply
with the grid charge
requirements stipulated in local
laws and regulations when this
function is enabled.
Set the grid charge cutoff SOC.
Application Scenario
Single inverter + Smart Dongle (WLAN-FE) + LUNA2000
connected to the management system
7 Man-Machine Interaction
Value Range
● Disable
● Enable
[20%, 100%]
96