Huawei SUN2000-3KTL-M1 Series User Manual page 51

Hide thumbs Also See for SUN2000-3KTL-M1 Series:
Table of Contents

Advertisement

SUN2000-(3KTL-10KTL)-M1 Series
User Manual
No.
J
K
Note 1:
● For details about how to operate the WLAN-FE Smart Dongle SDongleA-05,
● For details about how to operate the 4G Smart Dongle SDongleA-03, see
You can obtain the quick guide at
index.html
Note 2: For details about meter operations, see
Sensor Quick Guide
Manual, and
Note 3: SUN2000MA V100R001C00SPC142 and later versions can connect to
DTSU666-HW power meters.
Note 4: SUN2000MA V100R001C00SPC146 and later versions can connect to
YDS60-80 power meters.
Note 5: SUN2000MA V100R001C00SPC150 and later versions can connect to
YDS60-C24 power meters.
Note 6: SUN2000MA V100R001C00SPC160 and later versions can connect to
DTSU71 and DHSU1079-CT power meters.
Issue 17 (2024-01-12)
Component
AC switch
(Optional)
Smart Backup
Box
SDongleA-05 Smart Dongle Quick Guide (WLAN-FE) .
see
SDongleA-03 Quick Guide (4G) .
by searching for the Smart Dongle model.
DTSU666-H 100 A and 250 A Smart Power Sensor User
,
YDS60-C24 Smart Power Sensor Quick
Copyright © Huawei Technologies Co., Ltd.
Description
To ensure that the inverter can
be safely disconnected from the
power grid when an exception
occurs, connect an AC switch to
the AC side of the inverter.
Select an appropriate AC switch
in accordance with local
industry standards and
regulations. Huawei
recommends the following
switch specifications:
Recommended: a three-phase
AC circuit breaker with a rated
voltage greater than or equal
to 380 V AC and a rated
current of:
● 16 A (SUN2000-3KTL-M1,
SUN2000-4KTL-M1,
SUN2000-5KTL-M1, and
SUN2000-6KTL-M1)
● 25 A (SUN2000-8KTL-M1,
SUN2000-10KTL-BEM1 and
SUN2000-10KTL-M1)
Select a proper model as
required.
https://support.huawei.com/enterprise/en/
5 Electrical Connections
Source
Prepared by users
Purchased from
Huawei
DTSU666-HW Smart Power
Guide.
41