6.9 Air filter replacement
MX² 30
MX² 35-95
Figure 6.1 Tools required
The procedure for filter replacement is the same for process filter and reactivation filter. Replacement of
reactivation filter on MX² 55 shown as an example. The numbers within brackets refer to Figure 6.2 and
Figure 6.3 .
1. Set the mode switch to position 0.
2. Wait 60 seconds for the heater to cool down.
3. Set the main power switch to position 0 and lock the switch.
4. Open the filter box door by turning the lock counter clockwise (1).
5. Lift off the door (2).
6. Push the upper and lower filter clamp to release the filter (3).
7. Pull out the filter (4).
1
2
3
4
Figure 6.2
42
Service and maintenance
190TEN–1089–G1412