Schedules; Day/Night Schedule - heat-timer HWRQ Platinum Installation And Operation Manual

Hydronic/hot water outdoor reset multiple boiler heating controls
Table of Contents

Advertisement

SCHEDULES

Enter menu by pressing SELECT: Settings/Schedules
• T he HWRQ Platinum has two levels of heat. The Day Time level is used when a
building is occupied and people are active.
• T he Night Time (Setback) level is used when a building is not occupied, or when
people are sleeping.
• T he HWRQ Platinum can have up to four Day Time and four Night Time (Setback)
periods for each individual day of the week. The HWRQ Platinum will show which
period is it in on the 2nd line of the display.
• E very time the HWRQ Platinum updates the clock time, it checks the Day/Night
program. If there is a matching Day/Night time programmed, it sets the heat level
accordingly, otherwise, the heat level is not changed. This means you do not have to
program every day of the week.
• I f an office building is unoccupied all weekend, simply set the last programmed #4
setting (8:00 PM on Friday). Then, set all the Saturday and Sunday programs to **:**
(using the DEL button). The control will stay in Night Time (Setback) until it reaches
a Day setting (6:00AM on Monday).

DAY/NIGHT SCHEDULE

Day Time default is 6:00 am Night Time default is 10:00 PM
SELECT: Settings/Schedules/Day Night Schedule
• U se this setting to set up to 4 Day Time and 4 Night Time (Setback) settings per each
day of the week. The Day Time settings allows the HWRQ Platinum to set the Target
based on Outdoor temperature and the Reset ratio (when Reset is selected as a Control
Mode) or Set point (when Set Point is selected as a Control Mode).
• I f the Boost feature is being used, it uses the Day Time on the 1st setting of that day as a Boost calculation starting point.
• T he actual Boost start time varies depending on the Outdoor Temperature (OD).
• T he Night Time settings lets the HWRQ Platinum reduce the Target temperature (TGT) by the Night Setback setting.
Furthermore, if the Early Shutdown feature is being set, it uses the last Night Time setting of that weekday as an Early Shutdown
calculation starting point. In this case, the actual Early Shutdown start time will vary based on Outdoor temperature.
• I n this area of the menu 3 buttons will take effect. The NEXT button will allow the scroll between the 4 different settings of a
specific weekday. The BOILER/DAY button will allow the scroll between all weekdays. The PREV/DEL button will erase the
Day Time and Night Time settings for a specific day schedule.
Schedule Example
Schedule
MON
Day
6:00AM
#1
10:00PM ♦♦
Night
Day
**:**
#2
Night
**:**
Day
**:**
#3
Night
**:**
Day
**:**
#4
Night
**:**
♦ No boost will take effect.
♦♦ Early Shut Down ends. Night Schedule begins
Monday through thursday: V ari-Boost begins before 6 am and ends at 6 am
30
TUE
WED
6:00AM
6:00AM
10:00PM ♦♦
10:00PM ♦♦
**:**
**:**
**:**
**:**
**:**
**:**
**:**
**:**
**:**
**:**
**:**
**:**
D ay temperature level is maintained from 6 am until before 10 PM
E arly Shutdown starts before 10 PM and ends at 10 PM
N ight temperature level is maintained from 10 PM until the Vari Boost the following morning
Day of Week
THU
6:00AM
7:00AM
10:00PM ♦♦
11:00AM
**:**
1:00PM
**:**
4:00PM
**:**
6:00PM
10:00PM ♦♦
**:**
**:**
**:**
**:**
**:**
HWRQ Platinum Installation and Operation Manual
----- SCHEDULES -----
Day/Night Schedule
Copy Schedule
Set Date/Time
ALERT
The HWRQ Platinum will ignore any
Time setting that reads **:**
The #1 setting for any Day Time is
used by the Boost The last Night Time
setting is used by the Early Shutdown
ESD features
------ SCHEDULES ------
MON # 1
Day Time
Night Time
FRI
SAT
**:**
**:**
8:00AM ♦
4:00PM ♦♦
**:**
**:**
**:**
**:**
6:00Am
10:00Pm
SUN
**:**
**:**
**:**
**:**
**:**
**:**
**:**
**:**

Advertisement

Table of Contents
loading

Table of Contents