Analogue addressable smoke & rate or rise heat detectors with integrated isolator

Advertisement

Package Contents
1
Detector
1
Detector Base
Mounting Accessories
1
1
Manual
General
The user have to read carefully the following instructions, in order to be properly informed
and keep them for future use.
The BSR-6155 is an analogue addressable smoke detector which integrates the function of
optical smoke detection and it can work with any fire panel supports Olympia A Protocol. It
can be adjusted to detect multiple levels of smoke offering flexibility and rich functionality.
Also, it integrates a short circuit isolation circuit which is automatically activated and
disconnects the defective detector from the remaining loop, allowing it to be located by the
panel.
The detector sends to the main panel an analogue value which depends on the
concentration of smoke. The value is 100 in concentration of 0.107dB/m (small amount of
smoke) and increases proportionally to 120 in concentration of 0.300dB/m.
By default the panel is set to sound an alarm when the concentration of smoke is 0.107dB/m.
The user can change this setting from the panel for each detector and define any level of
smoke concentration between the lower and the upper limits, specifying the sensitivity of
the system depending on the requirements of each site.
The BSR-6157 is an analogue addressable smoke detector which integrates functions of
optical smoke and heat detection and it can work with any fire panel supports Olympia A
Protocol. It can be adjusted to detect multiple levels of smoke and heat offering flexibility and
rich functionality. Also, it integrates a short circuit isolation circuit which is automatically
activated and disconnects the defective detector from the remaining loop, allowing it to be
located by the panel.
The detector sends to the main panel an analogue value which depends on the
concentration of smoke and heat. The value is 100 in concentration of 0.107dB/m (small
o
amount of smoke) or a temperature of 57 C and increases proportionally to 120 in
concentration of 0.300dB/m or a temperature of 90 C. When a sudden increase in
temperature is detected the detector sends the value of 121.
By default the panel is set to sound an alarm when the concentration of smoke is 0.107dB/m
o
or the temperature is 57 C. The user can change this setting from the panel for each detector
and define any level of smoke concentration or temperature between the lower and the
upper limits, specifying the sensitivity of the system depending on the requirements of each
site. Also, the user can select A1R or A1S working mode through the panel.
The BSR-6160 is an analogue addressable heat detector which integrates the function of
rate-of-rise heat detection and it can work with any fire panel supports Olympia A Protocol. It
can be adjusted to detect multiple levels of heat offering flexibility and rich functionality.
Also, it integrates a short circuit isolation circuit which is automatically activated and
disconnects the defective detector from the remaining loop, allowing it to be located by the
panel.
The detector sends to the main panel an analogue value which depends on the heat. The
o
value is 100 at 57 C (A1R or A1S) or 89°C (CS) and increases proportionally to 120 at 90 C (A1R
or A1S) or 120°C (CS). When a sudden increase in temperature is detected the detector sends
the value of 121.
By default the panel is set to sound an alarm when the temperature reaches the lower level
of each working mode, namely 57°C (A1R or A1S) or 89°C (CS). The user can change this
setting from the panel for each detector and define any level of temperature between the
lower and the upper limits, specifying the sensitivity of the system depending on the
requirements of each site. Also, the user can select A1R, A1S or CS working mode through the
panel.
1
921615500, 921615700, 921616000_09_004
All detectors are composed by two parts. A plastic base which is placed on the ceiling and the main
body of the detector which fits on the plastic base with a simple rotation to the right. The detectors
o
have a 360 visible led and a remote led driver which are light up constantly in case of detection of
fire, till cancelled from the panel. Also, they are staying lit even if the sirens are silenced from the
panel, so the detector which detected the alarm is visible. They are turned off only when a reset
command is given from the panel. The indicator led blinks every 10 sec indicating the connection
status with the main panel.
SETTING THE ADDRESS
Each detector must have a unique address, with which it is recognised from the panel. It is forbidden
for two devices in the same loop to have the same address. To set it up you can use the function of
changing address point as described in the user manual of the panel.
INSTALLATION
For spacings, heights and all mounting points consult the local/national regulation or the standard
EN 54-14/2018. The detectors must be placed at least 50 cm away from fluorescent lamps. Cable
cross-section should be from 0.5 to 2.5mm .
MAINTENANCE & FUNCTIONAL TESTING
The detectors have fault diagnosis and dust compensation functions, which automatically informs
you when replacement or cleaning actions are required. These functions combined with periodic
manual testing ensure maximum security level. The manual testing procedure is carried out by
spraying a small amount of smoke into the detector with a testing spray or a counterpart product. It is
suggested to carry out a test every 6 months or after a change in the position of the sensor. A key
element of its proper function is the air to be able to freely circulate inside it. So be careful not to
block the openings of the outer cover. You can clean the detector by blowing clean pressurised air
from the outer side of the mesh. Before the manual testing it is suggested to enable the special "walk
in test" mode from the panel.
CAUTION !!
After installation the device must not be covered with dust or be painted or anything else happen
that will block the smoke to get to the sensor. Special attention must be given during the installation
and the use of the device, since the user assumes full responsibility for proper operation
o
afterwards.
Caution! Do not disassembly the detector for cleaning or for any other action.
Additional features of the device :
- Integration of dynamic algorithms for noise and false alarm rejection.
- Automatic fault diagnosis.
o
- 360 optically visible LED.
- Dust compensation and automatic generation of cleaning notifications. Stable level of
detection regardless of detector's working hours. (BSR-6155, BSR-6157)
- Compensation of smoke measurements based on ambient temperature which ensures high
precision measurements even under extreme environmental conditions. (BSR-6155, BSR-6157)
- Adjustable smoke and temperature alarm level for maximum flexibility. (BSR-6157)
- Adjustable smoke alarm level for maximum flexibility. (BSR-6155)
- Adjustable temperature alarm level for maximum flexibility. (BSR-6160)
o
UID:
In every device there is a double sticker with the UID (Unique Identifier) number. This number is
unique for each device.
During site works place the plastic cover to the detector (only for BSR-6155 & BSR-6157) as shown in
the picture above to protect the device from dust. Remove the plastic cover when all the site works
have finished.
2
2
921615500, 921615700, 921616000_09_004
Dimensional drawing (mm)
103
52
103
Installation
Remove the detector from its base by rotating counter-clockwise till the side marks are
aligned.
1
Fasten the base with the supplied mounting accessories.
2
3
921615500, 921615700, 921616000_09_004
48 55
103
17
103