V1.0-2023-10-30
Technical Data
Max. Output Apparent Power
Without Grid (VA)
*6
Max. Output Apparent Power
with Grid (VA)
Nominal Output Current (A)
Max. Output Current (A)
Max. Output Fault Current
(Peak and Duration) (A)
Inrush Current (Peak and
Duration) (A)
Maximum Output Overcurrent
Protection (A)
Nominal Output Voltage (V)
Nominal Output Frequency (Hz)
Output THDv (@Linear Load)
Efficiency
Max. Efficiency
European Efficiency
Max. Battery to AC Efficiency
MPPT Efficiency
Protection
PV String Current Monitoring
PV Insulation Resistance
Detection
Residual Current Monitoring
PV Reverse Polarity Protection
Battery Reverse Polarity
Protection
Anti-islanding Protection
GEH15-
GEH20-
3U-10
3U-10
15,000
20,000
(18,000
(24,000
@60s ,
@60s ,
24,000
32,000
@3s)
@3s)
15,000
20,000
22.7
30.3
22.7 (27.3
30.3 (36.4
@60s,
@60s,
36.4 @3s)
48.5 @3s)
71
10
Technical Parameters
GEH25-
GEH29�9-
3U-10
3U-10
25,000
30,000
(30,000
(36,000
@60sec)
@60sec)
25,000
29,900
37.9
45.5
37.9 (45.5
45.5 (54.5
@60s)
@60s)
94
264@53us
94
380/400
50/60
<3%
98.0%
97.5%
97.5%
99.9%
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
GEH30-
3U-10
30,000
(36,000
@60sec)
30,000
45.5
45.5 (54.5
@60s)