Start-Up, General; Unit Preparation; Additional Installation/Inspection; Gas Piping - Carrier 48FC M20 Series Service And Maintenance Instructions

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 17.5-27.5 nominal tons
Table of Contents

Advertisement

WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or
death.
The unit must be electrically grounded in accordance with lo-
cal codes and NEC ANSI/NFPA 70 (American National Stan-
dards Institute/National Fire Protection Association).
Proceed as follows to inspect and prepare the unit for initial
start-up:
1.
Remove all access panels.
2.
Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3.
Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspect for oil at all refrigerant tubing connections
and on unit base. Detecting oil generally indicates a
refrigerant leak. Leak-test all refrigerant tubing con-
nections using electronic leak detector, halide torch,
or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring connections.
Be sure that connections are completed and tight. Be
sure that wires are not in contact with refrigerant tubing
or sharp edges.
d. Inspect coil fins. If damaged during shipping and han-
dling, carefully straighten fins with a fin comb.
4.
Verify the following conditions:
a. Make sure that condenser-fan blade are correctly posi-
tioned in fan orifice. See Condenser Fan Adjustment sec-
tion for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.

START-UP, GENERAL

Unit Preparation

Make sure that unit has been installed in accordance with installa-
tion instructions and applicable codes.
In addition to the base unit start-up (unit with electro-mechanical
control), there are a few steps needed to properly start-up units
with optional direct digital controls (DDC). The DDC's Service
Test function should be used to assist in the base unit start-up
and also allows verification of output operation. Controller con-
figuration is also part of start-up. This is especially important
when field accessories have been added to the unit. The factory
pre-configures options installed at the factory. There may also be
additional installation steps or inspection required during the
start-up process.

Additional Installation/Inspection

Inspect the field-installed accessories for proper installation,
making note of which ones do or do not require configuration
changes. Inspect the DDC Alarms for initial insight to any po-
tential issues. Refer to the Controls, Start-up, Operation and
Troubleshooting Instructions manual for the specific DDC. In-
spect the SAT sensor for relocation as intended during installa-
tion. Inspect special wiring as directed below.

Gas Piping

Check gas piping for leaks.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in death, serious
personal injury and/or property damage.
Disconnect gas piping from unit when pressure testing at
pressure greater than 0.5 psig (3450 Pa). Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure testing
field-supplied gas piping at pressures of 0.5 psig or less, a unit
connected to such piping must be isolated by closing the
manual gas valve(s).
If the information in this manual is not followed exactly, a fire
or explosion may result causing property damage, personal in-
jury or loss of life.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified in-
staller, service agency or the gas supplier.
AVERTISSEMENT
RISQUE D´INCENDIE OU D´EXPLOSION
Si les consignes de sécurité ne sont pas suivies à la lettre, cela
peut entraîner la mort, de graves blessures ou des dommages
matériels.
Ne pas entreposer ni utiliser d´essence ni autres vapeurs ou liq-
uides inflammables à proximité de cet appareil ou de tout autre
appareil.
QUE FAIRE SI UNE ODEUR DE GAZ EST DÉTECTÉE
Ne mettre en marche aucun appareil.
Ne toucher aucun interrupteur électrique; ne pas
utiliser de téléphone dans le bâtiment.
Quitter le bâtiment immédiatement.
Appeler immédiatement le fournisseur de gaz en
utilisant le téléphone d´un voisin. Suivre les
instructions du fournisseur de gaz.
Si le fournisseur de gaz n´est pas accessible, appeler le
service d´incendie.
L´installation et l´entretien doivent être effectués par un instal-
lateur ou une entreprise d´entretien qualifié, ou le fournisseur
de gaz.

Return-Air Filters

Ensure correct filters are installed in unit (see Appendix B —
Physical Data). Do not operate unit without return-air filters.