Status Screen; Setpoint Screens; System Configuration Screens; Controller Configuration Screens - Carrier 50LCH Series Start-Up Instructions

Table of Contents

Advertisement

Screen
Name
Operation
Information
Operation
Indicators
Alarm
Description
ACCESS LEVEL
PASSWORD
Basic
None
User
1111
Service
Rolling
Factory
Rolling

STATUS SCREEN

The status screens can be accessed by pressing the status icon
from the main menu screen. The status screens are accessible for
all access levels. The types of status screens shown will depend on
the unit configuration. The status screens are not editable and will
display information about a specific component or system. See
Fig. 63 for status screen example.

SETPOINT SCREENS

The setpoint screens can be accessed by pressing the setpoints
icon from the main menu screen. The setpoint screen is only ac-
cessible with the user access level or higher and the available set-
point screens will vary based on the unit configuration. See Fig. 64
for setpoint screen layout.

SYSTEM CONFIGURATION SCREENS

The system configuration screen can be accessed by pressing the
system configuration icon from the main menu screen. The system
configuration screen is only accessible with the user access level
or higher and contains all user accessible configurations. See
Fig. 65 for the system configuration screen layout.

CONTROLLER CONFIGURATION SCREENS

The controller configuration screen is accessed by pressing the
Controller Configuration icon from the Main Menu screen. The
controller configuration screen is only accessible with the user ac-
cess level or higher and contains user accessible configurations re-
lated to control functions, such as time/date, communication, and
Fig. 62 — Home Screen Example
Table 8 — Control Access Levels
Access level at initial start-up or after a timeout has expired. Provides view only access to select setpoints and
settings. Not all screens will be viewable. Basic access can disable the unit.
Intermediate access to adjust setpoints and settings and access most screens. User can enable/disable the
unit, enable component and system tests, and acknowledge alarms.
Includes all User access, plus access to advanced setpoints and settings. Password is only available to factory
trained personnel. See Advanced Controls, Operation, and Troubleshooting Guide for information on obtaining
the service password or contact your local Carrier sales office for emergency service password access.
Factory use only.
DESCRIPTION
user password. See Fig. 66 for the Controller Configuration screen
layout.

CONTROLLER ID SCREEN

The controller ID screen is accessed by pressing the controller ID
icon from the Controller Configuration screen. The controller ID
screen is only accessible with the user access level or higher and
contains the unit model and serial number, software version, and
other control information. See Fig. 67 for the controller ID screen
layout.

START/STOP SCREEN

The start/stop screen can be accessed by pressing the start/stop
button
from the Home or Main Menu screen. With the basic
access level, the user can only disable unit operation or press
emergency stop (if the unit was running). User or higher access
level is required to enable unit operation, adjust the auto-restart
configuration, and access the schedule menu. User or higher ac-
cess level can also enable service run mode, enable component
test mode, and access the service tests screen when in service run
or component test mode. See Fig. 68 for the start/stop screen lay-
out (shown with user access level in Service Run mode). See Ta-
ble 9 for the start/stop screen functions.
39
Operating
Conditions
Key Setpoints
(Editable with Login
Status Shortcut