Camus Hydronics Valiant-FT II Series Installation And Service Manual page 30

Gas fired commercial condensing stainless steel boilers
Table of Contents

Advertisement

Outdoor Sensor Connected to Slave Boiler 2
Description
Slave boiler outdoor
sensor configuration
Outdoor temperature
sensor must be
connected to boiler
#2.
When done correctly,
the outdoor
temperature will be
shown on the Master
boiler
Electrical Connection(s)
Programming Instructions
Slave Boiler
1)
Press
and
2)
Press Sensor Configuration
3)
Select S5 (J8-11) Sensor
4)
Select Connector type = 10K single non-safety
5)
The control will proceed into a Lockout 2 condition
6)
Press [Verify] > [Begin] > [Yes]
7)
Press the reset button on the ignition control within the alotted time
Master Boiler
8)
Press
and
9)
Press [Lead Lag Master Configuration]
10) Press [Advanced Settings >]
11) Press the
to arrive at Outdoor Reset
12) Select Enable: Enabled
13) Select Maximum outdoor temperature (WWSD)
14) Select Minimum outdoor temperature (Outdoor design)
15) Select Low Water Temperature (Min. water temp)
16) Select Outdoor boost maximum off point (Design max.)
17) Press [Show Line] to confirm reset curve
18) Press the
to arrive at Warm Weather Shutdown
19) Select Enable = Shutdown after demand ends