Camus Hydronics Valiant-FT II Series Installation And Service Manual page 29

Gas fired commercial condensing stainless steel boilers
Table of Contents

Advertisement

Slave Boiler
Description
Slave boiler lead lag
setup
System temperature
sensor must be
connected to boiler
#1.
Outdoor temperature
sensor must be
connected to boiler
#2.
Master Boiler, System Sensor (Connected to Master Boiler #1)
Description
Master boiler system
sensor configuration
System temperature
sensor must be
connected to boiler
#1.
Outdoor temperature
sensor must be
connected to boiler
#2.
Electrical Connection(s)
Electrical Connection(s)
Programming Instructions
1)
Place toggle switch to LOCAL
2)
Press
and
3)
Select System Identification & Access
4)
Verify Modbus address. To be in sequential order
5)
Select Lead Lag Slave Configuration
6)
Select Slave Enabled = Enable slave for built-in Lead Lag master
The following steps are performed at the factory and verifying
on site will be sufficient:
7)
Select Pump Configuration
8)
Press [Advanced Options >>]
9)
Press the
to arrive at Central Heat Pump or DHW Pump
10) On Options:
Local burner demand
11) On Options: Local Lead Lag
12) Force On:
Outlet high limit
Programming Instructions
1)
Press
and
2)
Press [Sensor Configuration]
3)
Select S5 (J8-11) Sensor
4)
Connector Type: 10K NTC Single Non-Safety
5)
The control will proceed into a Lockout 2 condition
6)
Press [Verify] > [Begin] > [Yes]
7)
Press the reset button on the ignition control within the alotted time
25