Camus Hydronics Valiant-FT II Series Installation And Service Manual page 10

Gas fired commercial condensing stainless steel boilers
Table of Contents

Advertisement

Figure 12: Horizontal Vent Exhaust and Air Intake
Clearance
3.
Valiant FT can vent up to 100 equivalent feet.
Elbows can range from 3 to 5 feet in equivalent
length depending on the centerline radius.
Figure 13: Horizontal Vent Exhaust and Air Intake
Configurations and Clearance
Vent outlet shall terminate at least 12" (0.30m)
4.
away from any forced air inlet. The combustion air
intake should never terminate above the vent
outlet.
6