Toshiba MMD-UP0721HFP-UL Service Manual page 74

Air-conditioner multi type
Hide thumbs Also See for MMD-UP0721HFP-UL:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
01: TK1 oil
circuit trouble
02: TK2 oil
circuit trouble
H16
H16
1∗: Compressor
1 side
2∗: Compressor
2 side
H17
H17
L02
L02
L03
L04
L04
L05
No. of priority
indoor units
L06
L06
L07
L08
L08
L09
Location
Description
System status
of
detection
I/F
Oil level
All stop
detection
circuit trouble
Compressor
Compressor
All stop
P.C. board
trouble
(Step-out)
Indoor unit
Outdoor units
Stop of
model
corresponding
disagreement
unit
trouble
Indoor unit
Duplicated
Stop of
indoor header
corresponding
unit
unit
I/F
Duplicated
All stop
outdoor line
address
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
priority indoor
unit)
I/F
Duplicated
All stop
priority indoor
unit (as
displayed on
indoor unit other
than priority
indoor unit)
Indoor unit
Connection of
Stop of
group control
corresponding
cable to
unit
standalone
indoor unit
Indoor unit
Indoor group /
Stop of
addresses not
corresponding
set
unit
Indoor unit
Indoor capacity
Stop of
not set
corresponding
unit
- 74 -
Check code detection
Check items (locations)
condition(s)
No temperature change is
• Check for disconnection of
detected by TK1 despite
TK1 sensor.
compressor 1 having been
• Check resistance
started.
characteristics of TK1
sensor.
• Check for connection
trouble involving TK1 and
TK2 sensors
• Check for clogging in oil
equalizing circuit capillary.
• Check for refrigerant
entrapment inside
compressor.
No temperature change is
• Check for disconnection of
TK2 sensor.
detected by TK2 despite
compressor 2 having been
• Check resistance
started.
characteristics of TK2
sensor.
• Check for connection
trouble involving TK1 and
TK2 sensors
• Check SV3F valve
malfunction.
• Check for clogging in oil
equalizing circuit capillary.
• Check for refrigerant
entrapment inside
compressor.
Judged that the
• Check power supply
synchronization could not be
voltage.
taken.
(AC380V-415V ± 10%).
• Check for failure in
compressor.
• Check for possible cause
of abnormal overloading.
• Check for failure in outdoor
P.C. board (compressor).
In case of different outdoor
• Check outdoor unit model.
unit (Not corresponded to
(Check whether the
Air to Air Heat Exchanger
outdoor unit corresponds
type)
to Air to Air Heat
Exchanger type or not.)
There are more than one
• Check indoor addresses.
header units in group.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
There is duplication in line
• Check line addresses.
address setting for outdoor
units belonging to different
refrigerant piping systems.
More than one indoor units
• Check display on priority
have been set up as priority
indoor unit.
indoor unit.
More than one indoor units
• Check displays on priority
have been set up as priority
indoor unit and outdoor
indoor unit.
unit.
There is at least one
• Check indoor addresses.
standalone indoor unit to
which group control cable is
connected.
Address setting has not
• Check indoor addresses.
been performed for indoor
units.
Note:
This code is displayed
when power is turned on
for the first time after
installation.
Capacity setting has not
Set indoor capacity. (DN =
been performed for indoor
11)
unit.