Toshiba MMD-UP0721HFP-UL Service Manual page 105

Air-conditioner multi type
Hide thumbs Also See for MMD-UP0721HFP-UL:
Table of Contents

Advertisement

<RBC-AWSU52-UL>
1
Push the [
Menu] button to display the menu screen.
2
Push and hold the [
"Field setting menu".
• Push and hold the buttons for more than 4 seconds.
3
] / [
Push the [
screen, then push the
• When the group control is used, all the indoor units connected into the system are displayed on the screen.
4
Push the to select indoor unit in which you want to write the
setting data to EEPROM, then push the
• The setting display for the selected unit is displayed.
• The fan and louver of the indoor unit operate.
5
Move the cursor to select "Code (DN)" with the
"[0010]" with the [
6
Move the cursor to select "Data" with the [
[
] / [
] button to set the "Data" to each Type name of indoor unit.
For Outside Air type, set "Data" to [0016].
7
Push the [
Menu] button to set the other "Code(DN)" and "Data". After "Continue?" is
displayed on the screen, push the
8
Move the cursor to select "Code(DN)" with the
with the [
] / [
9
Move the cursor to select "Data" with the [
[
] / [
] button to set the "Data" to each capacity of indoor unit.
For 096 model, set "Data" to [0023].
10
Push the [
Menu] button to set the other "Code(DN)" and "Data". After "Continue?" is
displayed on the screen, push the No to finish the setting operation. " Setting" is displayed on
the screen for a while, then the screen returns to the "Field setting menu" screen.
11
Pushing the [
screen for a while when the single operation is used, then the screen returns to the "Field
setting menu" screen.
(It takes approx. 1 min until the remote controller operation is available again.)
12
Write the on-site setting data, such as an address setting, after installation to the EEPROM.
Perform the operation of
13
[
] button to select "Code(DN)", then set it to [0001] with the ]
Push the
]
[
] / [
(Filter sign lighting time)
14
Check the setting data displayed at this time with the setting data written down in [1] Setting
data read out from EEPROM.
If the setting data is different, set "Code(DN)" with the [
[
] to select "Data" and change it to the setting data written down in
[1] Setting data read out from EEPROM with the [
[
Menu] button.
If the setting data is the same, proceed to next operation.
Menu] button and the [
] button to select "7. DN setting" on the "Field setting menu"
[
Set/Fix ].
] / [
] button.
[
Set/Fix ].
] button.
Return] button on the unit selection screen displays "
1
4
to
again.
] button at the same time to display the
[
Set/Fix ].
[
] button, then set
] button, then push the
]
[
button, then set [0011]
] button then push the
] / [
] / [
- 105 -
Setting" on the
] button, push the
] button, then push the