[The example of Card Input 5 setting]
Code No. (DN) setting
Case.
[16A]
[16b]
[16C]
[16d]
[16F]
data
data
data
data
data
(1) 0000 0000 0027 0020 0000 0000 0000 0024 0024
(2)* 0000 0001 0027 0020 0003 0001 0001 0024 0024
(3)* 0000 0002 0027 0020 0003 0001 0001 0024 0024
(4) 0001 0000 0027 0020 0003 0001 0001 0024 0024
* The history operation mode is only recorded when the card is inserted even if the operation mode is changed when the
card is taken out, there is no related to the history operation mode.
[170]
[171]
[172]
[173]
Close (Status that card is inserted) Open (Status that card is taken n out)
data
data
data
data
• The operation mode continues running at the
same as the current mode.
• The setting temperature of cooling/dry and
heating mode is changed to 75.2ºF(24ºC) and
75.2ºF(24ºC) respectively due to change in
code No. 172, 173.
• The operation mode is running at the same
mode as the last time when the card was
inserted due to change in code no. 16b.
* The operation mode will be off if the mode
at the last time was in off operation. Also,
the fan speed will the same as the last time
when the card is inserted.
• The setting temperature of cooling/dry and
heating mode is changed to 75.2ºF(24ºC)
and 75.2ºF(24ºC) respectively due to
change in code No. 172, 173.
• The operation mode is running at the same
mode as the last time when the card was
inserted. Also, the operation mode will be
on even the mode was in off operation at
the last time due to change in code no.
16B.
* The fan speed will the same as the last
time when the card is inserted.
• The setting temperature of cooling/dry and
heating mode is changed to 75.2ºF(24ºC)
and 75.2ºF(24ºC) respectively due to
change in code No. 172, 173.
• The operation mode continues running
at the same as the current mode.
• The setting temperature of cooling/dry
and heating mode is changed to
75.2ºF(24ºC) and 75.2ºF(24ºC)
respectively due to change in code No.
172, 173.
External contact terminal
- 44 -
• The operation mode continues running at
the same as the current mode.
• The setting temperature of cooling/dry and
heating mode is changed to 80.6ºF(27ºC)
and 68ºF(20ºC) respectively due to change
in code No. 16C, 16d.
• The operation mode continues running
at the same as the current mode.
• The setting temperature of cooling/dry
and heating mode is changed to
80.6ºF(27ºC) and 68ºF(20ºC)
respectively due to change in code no.
172, 173.
• The fan speed for all operation modes is
changed due to change in code no.16F.
• The wind direction of Cooling/dry/fan
and heating mode are changed due to
change in code No. 170, 171 respectively.
Same operation as case (2)
• Due to change in code no. 16A, the
operation mode will be as below.
• When the operation is ON, the operation
mode will continue running at the same
as the current mode.
• When the operation is OFF, the air
conditioner will turn on automatically.
• The setting temperature of cooling/dry and
heating mode is changed to 80.6ºF(27ºC)
and 68ºF(20ºC) respectively due to change
in code No. 172, 173.
• The fan speed for all operation modes is
changed due to change in code no.16F.
• The wind direction of Cooling/dry/fan and
heating mode are changed due to change
in code No. 170, 171 respectively.