Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
H05
H05
H06
H06
H07
H07
01: TK1 sensor
trouble
02: TK2 sensor
trouble
H08
H08
H15
H15
Location
Description
System status
of
detection
I/F
TD1 sensor
All stop
miswiring
(incomplete
insertion)
Activation of
I/F
All stop
low-pressure
protection
I/F
Low oil level
All stop
protection
I/F
Trouble in
All stop
temperature
sensor for oil
level detection
All stop
I/F
TD2 sensor
All stop
miswiring
(incomplete
insertion)
- 73 -
Check code detection
Check items (locations)
condition(s)
Discharge temperature of
• Check installation of TD1
compressor 1 (TD1) does
sensor.
not increase despite
• Check connection of TD1
compressor being in
sensor connector and
operation.
wiring.
• Check resistance
characteristics of TD1
sensor.
• Check for failure in outdoor
P.C. board (I/F).
• Check service valves to
Low-pressure Ps sensor
detects operating pressure
confirm full opening
lower than 0.02MPa.
(both gas and liquid sides).
• Check outdoor PMVs for
clogging (PMV1, 2, 3).
• Check for failure in SV4
circuits.
• Check for failure in low-
pressure Ps sensor.
• Check indoor filter for
clogging.
• Check valve opening
status of indoor PMV.
• Check refrigerant piping for
clogging.
• Check operation of outdoor
fan (during heating).
• Check for insufficiency in
refrigerant quantity.
Operating compressor
<All outdoor units in
detects continuous state of
corresponding line to be
low oil level for about 2
checked>
hours.
• Check connection and
installation of TK1 and TK2
sensors.
• Check resistance
characteristics of TK1 and
TK2 sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
problem inside compressor
casing.
• Check SV3D, SV3F valves
for failure.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.
Sensor resistance is infinity
• Check connection of TK1
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK1
sensor.
• Check for failure in outdoor
P.C. board (I/F).
Sensor resistance is infinity
• Check connection of TK2
or zero (open/short circuit).
sensor connector.
• Check resistance
characteristics of TK2
sensor.
• Check for failure in outdoor
P.C. board (I/F).
Discharge temperature of
• Check installation of TD2
(TD2) does not increase
sensor.
despite compressor 2 being
• Check connection of TD2
in operation.
sensor connector and
wiring.
• Check resistance
characteristics of TD2
sensor.
• Check for failure in outdoor
P.C. board (I/F).