Toshiba MMD-UP0721HFP-UL Service Manual page 69

Air-conditioner multi type
Hide thumbs Also See for MMD-UP0721HFP-UL:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
00:
Capacity over
01-:
No. of units
connected
E16
E16
E18
00:
No header unit
02:
Two or more
E19
E19
header units
01:
Connection of
outdoor unit
from other line
E20
E20
02:
Connection of
indoor unit
from other line
E23
E23
E25
E25
Address of
outdoor unit
from which
signal is not
received
normally
E26
E26
Location
Description
System status
of
detection
I/F
Too many
All stop
indoor units
connected
Indoor unit
Trouble in
Stop of
communication
corresponding
between indoor
unit
header and
follower units
I/F
Trouble in
All stop
number of
outdoor header
units
I/F
Connection to
All stop
other line found
during
automatic
address setting
I/F
Outdooroutdoor
All stop
communication
transmission
trouble
I/F
Duplicated
All stop
follower outdoor
address
I/F
Signal lack of
All stop
outdoor unit
- 69 -
Check code detection
Check items (locations)
condition(s)
• Combined capacity of
• Check capacities of indoor
indoor units is too large.
units connected.
• Check combined HP
Note:
capacities of indoor units.
If this code comes up
• Check HP capacity
after backup setting for
settings of outdoor units.
outdoor unit failure is
• Check No. of indoor units
performed, perform "No
connected.
capacity over detected"
• Check for failure in outdoor
setting.
P.C. board (I/F).
<"No capacity over detected"
setting method>
Turn on SW103 / Bit 3 on I/F
P.C. board of outdoor header
unit.
For Cooling Only model,
this check code is not
displayed even if it exceeds
the combined capacity of
indoor units.
• More than 128 indoor units
are connected.
Periodic communication
• Check remote controller
between indoor header and
wiring.
follower units cannot be
• Check indoor power supply
maintained.
wiring.
• Check P.C. boards of
indoor units.
• There are more than one
Outdoor header unit is
outdoor header units in
outdoor unit to which indoor-
one line.
outdoor tie cable (U1,U2) is
• There is no outdoor header
connected.
unit in one line.
• Check connection of
indoor-outdoor
communication line.
• Check for failure in outdoor
P.C. board (I/F).
Equipment from other line is
Disconnect inter-line tie
cable in accordance with
found to have been
connected when indoor
automatic address setting
automatic address setting is
method explained in
in progress.
"Address setting" section.
Signal cannot be transmitted
• Check power supply to
to other outdoor units for at
outdoor units. (Is power
turned on?)
least 30 seconds
continuously.
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for failure in outdoor
P.C. board (I/F).
• Check termination
resistance setting for
communication between
outdoor units.
There is duplication in
Note:
outdoor addresses set
Do not set outdoor
manually.
addresses manually.
Outdoor unit initially
• Backup setting is being
communicating normally
used for outdoor units.
fails to return signal for
• Check power supply to
specified length of time.
outdoor unit. (Is power
turned on?)
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for failure in outdoor
P.C. board (I/F).