[3] Writing the setting data to EEPROM
The settings stored in the EEPROM of the P .C. board for indoor unit servicing are the factory-set values.
Step 1
In STOP status, push [MENU] and [▼] buttons simultaneously for at least 10 seconds.
• In the air-conditioning group control mode,
system address (the value of the refrigerant piping system is the same as the number of outdoor units,
and one outdoor unit is displayed as 1). The indoor unit address is represented by N. The indoor unit
number displayed first is the main indoor unit number.
• In the non-group control mode (only one indoor unit), only 1-1 is displayed on the left.
(If the auto-address setting mode is interrupted in [2] step 2a, the unit No. [all] is displayed)
Step 2
Push [▼] or [▲] button to adjust the indoor unit number. The indoor unit number in the group control will
be changed cyclically. Select an indoor unit to change the settings and push [TIME] button to confirm.
The fan of the selected indoor unit starts its operation and the swing operation of the louvers starts after
confirmation.
(If [all] is displayed, directly push [TIME] button to enter the DN setting mode.)
CODE No. is displayed as [10] for the first time.
Step 3
Set the indoor unit type and capacity
(This data has been written to EEPROM at the factory by changing the type and capacity code.)
1. CODE No. is displayed as [10] for the first time.
2. Use [MENU] button to adjust the flash from CODE No. to
SET DATA on the left. Push [▼] or [▲] button to select the type.
(For example, 4way Air Cassette type is set to [0001].
Refer to table 2)
3. Push [MENU] button to adjust the flash to CODE No. on the
right after pushing [TIME] button to confirm.
(If the setting data is displayed, the operation is completed.)
4. Press [▼] or [▲] button to set the CODE No. to [11].
5. Use [MENU] button to adjust the flash from CODE No. to
SET DATA on the left. Push [▼] or [▲] button to select
the capacity.
(For example, 80 Type is set to [0012]. Refer to table 3)
6. Push [MENU] button to adjust the flash to CODE No. on the
right after pushing [TIME] button to confirm.
(If the setting data is displayed, the operation is completed.)
7. Push [ON/OFF] button to complete the setting when the
setting is completed.
When [ON/OFF] button is pushed,
display disappears and the air conditioner enters the normal stop mode.
(When
Step 4
Write the setting data on the site (such as address setting, etc.) into the EEPROM, and then turn off the
remote controller after confirming.
Step 5
Repeat steps 1, 2 and push [▼] or [▲] button to adjust the CODE No. to check the setting data (SET
DATA) and compare it with the data recorded in [1].
If the result is different, change the setting data of the corresponding CODE No. to the data recorded in [1]
according to step 3.
If the result is same, proceed to the next step.
Step 6 Push [ON/OFF] button to complete the setting when the setting is completed.
When [ON/OFF] button is pushed,
normal stop mode.
(When
flashes, it cannot receive operation instructions from the remote controller.)
flashes, it cannot receive operation instructions from the remote controller.)
flashes, then the display disappears and the air conditioner enters the
and the indoor unit No.1-N are displayed. 1 is the piping
SET DATA [MENU]
flashes, then the
– 56 –
[TIME]
[▼]
[▲]
[ON/OFF]
CODE No.