[E04 error]
Does outdoor operate?
YES
Check indoor P.C. board.
Defect → Replace
[E10 error]
Is there no disorder of power supply?
NO
Check indoor control P.C. board
(MCC-1643).
Defect → Replace
NO
Is group address setup of
remote controller correct?
Are wiring in indoor unit and
1, 2, 3 inter-unit cables correct?
Are wirings of terminal blocks
(1, 2, 3) wired to CN67 normal?
Does the voltage
between 2 and 3 of the indoor unit
inter-unit terminal blocks
(1, 2, 3) vary?
Check outdoor P.C. board.
Defect → Replace
YES
NO
YES
NO
YES
NO
YES
NO
∗ As shown in the following figure,
carry out measurement within 20 seconds
after the power was turned on.
Black
White
Terminal block
– 44 –
Check CODE No. [14].
Correct wiring and
inter-unit cables.
Correct wiring of connector
and terminal blocks.
Check indoor P.C. board
(MCC-1643).
Defect → Replace
S5277G
3
2
1
Check power supply voltage.
Correct lines.
Check and eliminate noise, etc.