Toshiba RAV-HM561KRTP-E Installation Manual
Hide thumbs Also See for RAV-HM561KRTP-E:

Advertisement

Installation Manual
Indoor Unit
Model name:
High-Wall Type
RAV-HM561KRTP-E
RAV-HM801KRTP-E
RAV-HM901KRTP-E
For commercial use
Installation Manual
R32
English
1

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba RAV-HM561KRTP-E

  • Page 1 Installation Manual Indoor Unit Model name: For commercial use High-Wall Type RAV-HM561KRTP-E RAV-HM801KRTP-E RAV-HM901KRTP-E English Installation Manual...
  • Page 2: Table Of Contents

    Be sure to check the refrigerant type for outdoor unit to be combined, and then install it. Product information of ecodesign requirements. (Regulation (EU) 2016/2281) http://ecodesign.toshiba-airconditioning.eu/en Contents PRECAUTIONS FOR SAFETY ..........5 ACCESSORY PARTS .
  • Page 3 The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation...
  • Page 4 Installation Manual Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
  • Page 5 Installation Manual Warning indications on the air conditioner unit Warning indication Description WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies Disconnect all remote electric power supplies before servicing. before servicing. WARNING WARNING Moving parts. Moving parts.
  • Page 6: Precautions For Safety

    Installation Manual PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. •...
  • Page 7 Installation Manual • Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the front panel of the indoor unit to undertake work. • Wear protective gloves and safety work clothing during installation, servicing and removal.
  • Page 8 Installation Manual Selection of installation location • When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. • Do not install the air conditioner in a location that may be subject to a risk of exposure to a combustible gas.
  • Page 9 Installation Manual Refrigerant piping • Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury. •...
  • Page 10 Installation Manual • Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is extended may give rise to smoking and/or a fire. • Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
  • Page 11 Installation Manual Relocation • Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result. •...
  • Page 12: Accessory Parts

    Installation Manual ACCESSORY PARTS Part name Q’ty Shape Usage (Hand over to customers) (For other languages that do not appear in Installation Manual This manual this installation Manual, please refer to the enclosed CD-R.) (Hand over to customers) (For other languages that do not appear in Owner’s Manual this Owner’s Manual, please refer to the enclosed CD-R.)
  • Page 13: Selection Of Installation Place

    Installation Manual SELECTION OF INSTALLATION PLACE WARNING • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. CAUTION • Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
  • Page 14 Installation Manual Installation diagram of Indoor unit For the rear left and left piping Before installing the wireless remote controller Hook Wall 1. Remove the battery cover. Installation 2. Insert 2 new batteries plate (R03 [AAA] type) following the (+) and (−) Insert the cushion between the positions.
  • Page 15: Installation Of Indoor Unit

    Installation Manual Wireless remote controller • A place where there are no obstacles such as a curtain that may block the signal from the indoor unit. • Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
  • Page 16: Cutting A Hole And Mounting Installation Plate

    Installation Manual CUTTING A HOLE AND MOUNTING INSTALLATION PLATE Cutting a hole When the installation plate is directly mounted on the wall In case of installing the refrigerant pipes from the rear: 1. Securely fit the installation plate onto the wall by screwing it in the upper and lower Decide the hole position for piping at parts to hook up the indoor unit.
  • Page 17: Piping And Drain Hose Installation

    Installation Manual PIPING AND DRAIN HOSE INSTALLATION Piping and drain hose forming * Since dewing results in a machine trouble, make sure to insulate both connecting pipes. (Use polyethylene foam as insulating material.) Rear right Rear left Bottom left Left Bottom right Right 1.
  • Page 18 Installation Manual How to remove the drains cap Clip the drain cap by needle-nose pliers and pull out. How to fix the drains cap 1) Insert hexagonal wrench (dia. 4 mm) in a centre head. 2) Firmly insert drains cap. Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap.
  • Page 19 Installation Manual In case of bottom right or bottom left piping • After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool. Slit Left-hand connection with piping Bend the connecting pipe so that it is laid within 43 mm above the wall surface.
  • Page 20 Installation Manual Gas side Heat insulator provided Indoor unit shield pipe Liquid side Cut the heat insulator of the gas pipe (locally procured) leaving a 10 mm overlap with the shield of the shield pipe. Heat insulator wrapping cross section A-A Make the slit part of heat insulator to upward.
  • Page 21: Indoor Unit Fixing

    Installation Manual INDOOR UNIT FIXING DRAINAGE 1. Pass the pipe through the hole in the wall, 1. Run the drain hose sloped downwards. and hook the indoor unit on the installation NOTE plate at the upper hooks. • Hole should be made at a slight downward 2.
  • Page 22: Refrigerant Piping

    Installation Manual REFRIGERANT PIPING Refrigerant Piping Permissible Piping Length and Height Difference 1. Use copper pipe with 0.8 mm or more thickness. (In case pipe size is dia. 15.9, They vary according to the outdoor unit. with 1.0 mm or more.) For details, refer to the Installation Manual 2.
  • Page 23 Installation Manual REQUIREMENT CAUTION Tightening with an excessive torque may crack • Do not scratch the inner surface of the flared the nut depending on installation conditions. part when removing burrs. Tighten the nut within the specified tightening • Flare processing under the condition of torque.
  • Page 24 Installation Manual Open fully valves of the outdoor Wireless remote controller A-B unit selection Open the valve of the outdoor unit fully. Using 2 wireless remote controllers for the A hexagonal wrench is required for opening the respective air conditioners, when the 2 air valve.
  • Page 25: Electrical Connection

    Installation Manual ELECTRICAL CONNECTION WARNING • Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces applied to the terminals from affecting the terminals. Incomplete connection or fixation may cause a fire or other trouble. •...
  • Page 26 Installation Manual CAUTION The remote controller wire and Indoor / Outdoor connecting wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other factor. Communication type TU2C-Link can be used with these models.
  • Page 27 Installation Manual Wiring between indoor unit and outdoor unit Figure below shows the wiring connections between the indoor and outdoor units and between the indoor units and remote controller. The wires indicated by the broken lines or dot-and-dash lines are provided at the locally. Refer to the both indoor and outdoor unit wiring diagrams.
  • Page 28 Installation Manual Wired remote controller wiring • As the wired remote controller wire has non-polarity, there is no problem if connections to indoor unit terminal blocks A and B are reversed. Wiring diagram Terminal block for remote controller Terminal block wiring of indoor unit Wired remote controller unit...
  • Page 29 Installation Manual Wiring Connection Power supply terminal block How to connect the power supply wiring Terminal cover and control wiring The power supply wire and the control wire can be Screw connected without removing the front panel. Terminal block for REQUIREMENT communication/ remote controller...
  • Page 30 Installation Manual Wiring connection (twin, triple, Clamp the wired remote controller wire double twin system) with the cord clamp. Install the clamp base with a screw. Connect a header unit by following the Insert the Indoor / Outdoor connecting procedure of wiring connection for single wires fully into the terminal block and system.
  • Page 31: Applicable Controls

    Installation Manual APPLICABLE CONTROLS • For using the wired remote controller RBC-AMS55E , refer to the Owner’s Manual attached to the wired remote controller. Applicable controls setup REQUIREMENT (settings at the site) • When you use this air conditioner for the first time, it takes approx.
  • Page 32 Installation Manual Change of lighting time of filter Each time [ ] setting button is pushed, indoor unit numbers in the group sign control change cyclically. Select the indoor According to the installation condition, the lighting unit to change settings for. time of the filter sign (Notification of filter cleaning) •...
  • Page 33 Installation Manual Remote controller sensor 8°C operation The temperature sensor of the indoor unit Pre-heating operation can be set for cold regions senses room temperature usually. Set the remote where room temperature drops to below zero. controller sensor to sense the temperature around Follow to the basic opreration procedure the remote controller.
  • Page 34 Installation Manual Adjustment of air direction Group control 1. Using the remote controller switch, change the Simultaneous twin system up/down air direction by moving the horizontal A combination with an outdoor unit allows louver. simultaneous ON / OFF operation of the indoor 2.
  • Page 35 Installation Manual Group control for system of multiple units One group can control up to 16 (TU2C-Link) or 8 (TCC-Link) indoor units with one remote controller. (Refer to the Wiring specifications) Group control in single system Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit...
  • Page 36 Installation Manual Manual address setting Push and hold menu button and [ ] setting button simultaneously for 10 seconds or more. Push OFF timer button to confirm the selected indoor unit. <Line address> Push the menu button until the Code No. flashes. And using the [ ] buttons, specify the Code [12] Push the menu button until the Set data flashes.
  • Page 37 Installation Manual Central control system Air conditioners at multiple locations can be controlled individually for each refrigeration system from a control room. Central control is not available with the supplied wireless remote controller. Use the optional wired remote controller. Wiring for central control The terminal block for central control wiring ) is the same as that for optional wired remote controller.
  • Page 38 Installation Manual Centrally control the system by the SDI, DI series on their own setting for the terminating resistor is required. • Use switch SW01 for the setting. • Make the terminating resistor setting only for the indoor unit with the smallest line address number. Central Central control...
  • Page 39 Installation Manual How to set the SW01 Remove the electrical control box cover and set bit1 of SW01 on the board to ON. Remove the front panel. (Do not touch SW02 as it is used for other • Before removing the front panel, direct the setting.) horizontal louver to the direction shown in the figure below.
  • Page 40 Installation Manual Centrally control the system by connecting to the TCC-LINK central control system. Setting central control addresses When air conditioners of the SDI, DI series are connected to the TCC-LINK central control system for central control using this product, set the addresses of indoor units using the following procedure. Completion of ELECTRIC WORK construction System power ON...
  • Page 41: Test Run

    Installation Manual TEST RUN A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Before test run Wired remote controller Be sure to stop the air conditioner before • Before turning on the power supply, carry out making settings.
  • Page 42 Installation Manual After the test run, push OFF timer button to Repeat procedures → → → stop a test run. Indicators “Operation” (green), “Timer” ([TEST] disappears on the display and the air (green), and “Ready” (orange) in the conditioner enters the normal stop mode.) wireless receiver section flash in approx.
  • Page 43 Installation Manual When a test run is not Monitoring function performed properly This function can be used to call the service monitor mode from the remote controller during a • When a test run is not performed properly, refer test run to obtain the temperature of the sensors to the error code and the part to be checked on of the remote controller, indoor unit, and outdoor “Troubleshooting”.
  • Page 44 Installation Manual In case of wireless remote controller Indoor unit data (Forced test operation is performed in a Code No. Data name different way.) Room temperature (remote controller) Indoor unit intake air temperature (TA) REQUIREMENT Indoor unit heat exchanger (coil) •...
  • Page 45: Maintenance

    Installation Manual MAINTENANCE Mount the air filter Daily maintenance Cleaning of air filter Turn on the circuit breaker, then push the button on the remote controller to start Push the button to stop the operation, the operation. then turn off the circuit breaker. After the cooling or dry operation, the CAUTION ventilation fan keeps running for...
  • Page 46 Installation Manual Periodic maintenance For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner. When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended. Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof treatment, if necessary.
  • Page 47: Troubleshooting

    Installation Manual TROUBLESHOOTING Confirmation and check If a problem occurs with the air conditioner, the OFF timer indicator alternately shows the check code and the indoor Unit No. in which the problem occurred. Check code The indoor Unit No. in which the problem occurred.
  • Page 48 Installation Manual Error codes and parts to be checked Wired Wireless remote controller remote Sensor block display of controller receiving unit Judging Air conditioner display Main defective parts Parts to be checked / error description device status Operation Timer Indication Ready Flashing GR GR OR...
  • Page 49 Installation Manual Wired Wireless remote controller remote Sensor block display of controller receiving unit Judging Air conditioner display Main defective parts Parts to be checked / error description device status Operation Timer Indication Ready Flashing GR GR OR Room temp. sensor (TA), indoor P.C. board Indoor unit room temp.
  • Page 50 Installation Manual Wired Wireless remote controller remote Sensor block display of controller receiving unit Judging Air conditioner display Main defective parts Parts to be checked / error description device status Operation Timer Indication Ready Flashing GR GR OR Indoor fan motor, indoor P.C. board --- Indoor unit fan error Indoor Indoor AC fan error (fan motor thermal...
  • Page 51: Specifications

    Installation Manual SPECIFICATIONS Sound pressure level (dBA) Model Weight (kg) Cooling Heating RAV-HM561KRTP-E RAV-HM801KRTP-E RAV-HM901KRTP-E * Under 70 dBA ‒ 50 ‒ 50-EN...
  • Page 52 Installation Manual Declaration of Conformity Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. 144/9 Moo 5, Bangkadi Industrial Park, Tivanon road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TCF holder: TOSHIBA CARRIER EUROPE S.A.S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below:...
  • Page 53 Installation Manual Declaration of Conformity Manufacturer: Toshiba Carrier (Thailand) Co., Ltd. 144/9 Moo 5, Bangkadi Industrial Park, Tivanon road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand TCF holder: TOSHIBA CARRIER UK LTD. Porsham Close Belliver Industrial Estate Roborough Plymouth Devon...
  • Page 54: Appendix

    Installation Manual APPENDIX 5. When a commercially available dryer is Work instructions attached to the existing pipes. The existing R22 and R410A piping can be reused • There is the possibility that copper green rust for inverter R32 product installations. has been generated.
  • Page 55 Installation Manual Existing pipes: Cannot be used. Are there scratches or dents on the existing pipes? Use new pipes. Is it possible to operate the existing air conditioner? After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer,* recover the refrigerant.
  • Page 56 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand 1122750197...

This manual is also suitable for:

Rav-hm801krtp-eRav-hm901krtp-e

Table of Contents