Toshiba RAV-HM301SDTY-E Service Manual page 31

Hide thumbs Also See for RAV-HM301SDTY-E:
Table of Contents

Advertisement

No.
Item
Save operation
18
19
8°C heating/Frost
protective operation
Outline of specifications
1) The current release control is performed with the
restriction ratio set in EEPROM on the outdoor unit.
2) Setting method: push and hold [MENU] and [▼]
buttons on the remote controller for at least 10 seconds
to enter DN setting, adjust CODE No. to [C2] and
change the SET DATA.
3) The factory default setting of SET DATA is 75, which is
75% power level. Each time push [▼] or [▲] button,
the system will change the power level by 1% within
100% to 50%.
4) Push [ON/OFF] button to complete the setting after
pushing [TIME] button to confirm.
1) This functional is intended for the cold latitudes and
performs objective heating operation
(8°C heating operation).
2) This function is valid only for combination with the
outdoor units.
3) Using the indoor CODE No. [D1] (1 bit), Valid/Invalid of
this function is set up at the customer's side.
∗ The setup by CODE No. is Invalid [0]/Valid [1] and
Invalid [0] has been set at the shipment.
4) This operation is the heating operation which sets 8°C
as the setup temperature of the target.
5) This function starts operation by pushing button [▼]
during heating operation; besides by pushing [▼]
button for 4 seconds or more after temperature reached
the minimum set temperature.
6) To stop/release this operation, select and execute one
from the following operations.
Push [▲] button: Heating operation (18°C setting)
continues.
Push [ON/OFF] button: Air conditioner stops.
(Heating 18°C operation at the next start)
Push [MENU]: Other operation mode is selected and the
operation continues.
7) As the setup temperature is 8°C and the human heating is
not targeted, the cold air discharge preventive control
(Item 7) is made invalid to suppress the intermittent
operation.
8) The settings of the air direction and air volume are
changeable during this operation.
9) The indoor fan stops to protect the compressor for
2 minutes after start of heating operation
(Thermo-ON) by this function.
– 31 –
Remarks
This function depends
on remote controller
In a group connection,
if there is even one
combination with other
unit, "This function is not
provided." is displayed.
The setup temperature
jumps from [18] to [8].