16. Replace cover and tighten screws to 60 in-lb (6.8 n-m) of torque.

LP II SERIES REMOTE MODEL ONLY

Input Power Connections
1. Refer to Figures 4 or 5 and 6 when connecting input power to the unit.
2. Loosen set screw that locks cover in place.
3. Unscrew the housing cover and remove.
Note: Two threaded female conduit openings are provided in the remote housing to separate input and output
wiring from the remote fork wiring.
4. Pull approximately 6" (15.24 cm) of cable through conduit closest to grounding bracket and strip as
follows:
a. Ground –
/
" (9 to 10 mm)
3
8
b. Power Leads –
5. Attach incoming ground lead to grounding bracket as shown in Figure 6.
Note: The LP II incorporates pluggable terminal blocks for ease of connection. If the terminal block is unplugged
while making connections, ensure it is seated properly when reinstalled.
6. Attach power leads to terminal block as shown in Figure 4 or 5.
7. Check that all wires are held tightly in place by lightly pulling each conductor.
Main Relay Connections
8. Refer to Figures 4 or 5 and 7 when connecting to the main relay.
9. Pull approximately 9" (22.86 cm) of cable through conduit and strip
10. Attach leads to terminal block as shown in Figure 7.
11. Check that all wires are held tightly in place by lightly pulling each conductor.
Auxiliary Relay Connections - ADVANCED ONLY
12. Refer to Figures 5 and 8 when connecting to the auxiliary relay.
13. Pull approximately 2.5" (6.35 cm) of cable through conduit and strip
14. Attach leads to terminal block as shown in Figure 8.
15. Check that all wires are held tightly in place by lightly pulling each conductor.
Remote Fork Connections
16. Refer to Figure 9 or 10 and 11 when connecting the remote fork.
17. Pull approximately 2.5" (6.35 cm) of cable through conduit and strip
18. Connect factory supplied cable to terminals block as shown in Figure 11.
19. Check that all wires are held tightly in place by lightly pulling each conductor.
LVP180613 Rev. B
/
" (6 to 7 mm)
1
4
/
" (6 to 7 mm).
1
4
/
" (6 to 7 mm).
1
4
/
" (4 to 5 mm).
3
16
9
www.bindicator.com