ELECTRICAL CONNECTIONS

Note: The LP II can be operated from 120-240 VAC 50/60 Hz or 24-48 VDC and provides reverse polarity
protection in the event of a wiring error.

LP II SERIES INTEGRAL MODEL ONLY

Input Power Connections
1. Refer to Figures 4 or 5 and 6 when connecting input power to the unit.
2. Loosen the housing cover screws and remove cover.
CAUTION: IF THE UNIT WAS SUPPLIED WITH A GASKET AVOID FOLDING, CUTTING, OR TEARING
GASKET. DAMAGING THE GASKET CAN ALLOW MOISTURE TO ENTER THE ENCLOSURE AND
DAMAGE THE UNIT.
Note: Two threaded female conduit openings are provided in the housing to separate input and output wiring.
3. Pull approximately 4.5" of cable through conduit closest to the grounding bracket and strip as follows:
a.
Ground –
/
" (9 to 10 mm)
3
8
b. Power Leads –
4. Attach incoming ground lead to grounding bracket as shown in Figure 6.
Note: The LP II incorporates pluggable terminal blocks for ease of connection. If the terminal block is unplugged
while making connections, ensure it is seated properly when reinstalled.
5. Attach power leads to terminal block as shown in Figure 4 or 5.
6. Check that all wires are held tightly in place by lightly pulling each conductor.
Main Relay Connections
7. Refer to Figures 4 or 5 and 7 when connecting to the main relay.
8. Pull approximately 4.5" (11.43 cm) of cable through conduit and strip
9. Attach leads to terminal block as shown in Figure 6.
10. Check that all wires are held tightly in place by lightly pulling each conductor.
For STANDARD models skip to Step 15; for ADVANCED models continue to Step 11.
Auxiliary Relay Connections - ADVNACED ONLY
11. Refer to Figures 4 or 5 and 8 when connecting to the auxiliary relay.
12. Pull approximately 5.5" (13.97 cm) of cable through conduit and strip
13. Attach leads to terminal block as shown in Figure 6.
14. Check that all wires are held tightly in place by lightly pulling each conductor.
15. Reinstall the gasket, if necessary.
/
" (6 to 7 mm)
1
4
/
" (6 to 7 mm).
1
4
/
" (6 to 7 mm).
1
4
8
www.bindicator.com
LVP180613 Rev. B