48 Start-up and validation test
Action
Make sure that the correct indications are activated: the SMT fault and other indications depend-
ing on the parameter settings and if an FSO module is installed.
Make sure that the STO is activated and that the motor coasts to a stop.
Make sure that you cannot start the drive before you reset the drive.
Reset the drive. Make sure that you cannot reset and restart the drive before the resistance in
the XFLT input increases to more than 50 ohm (that is, the jumper wire connected earlier is re-
moved).
Restart the drive and the motor. Make sure that they operate normally.
If used, do the overtemperature monitoring and short-circuit detection tests for the XWRN input.
Make sure that the motor temperature warning indication is activated in both cases.
Create a backup file of the drive parameters with the Drive composer PC tool or control panel.
If you use an FSO module, save the FSO safety file (button Save safety file in the Drive composer
pro PC tool).
Fill in and sign the validation test report. Store the report in the logbook of the machine.