Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).
Example of supply cable calculation
I
= 128 A, maximum ambient temperature is 30 °C, maximum fuse = 200 A
Package
• Single supply cables (3 phases + PE):
• I = 128 A + 25 % = 128 x 1.25 = 160 A
• For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
• So use a cable of 3 x AWG2/0 + AWG4
• Parallel supply cable 2 x (3 phases + PE):
• I = (128 A + 25 %)/2 = (128 x 1.25)/2 = 80 A
• For AWG4, the maximum current is 85 A, which is sufficient => use AWG4
• So use a cable of 2x (3 x AWG4 + AWG8)