Technical characteristics
Voltage
Frequency
External fuse
Contact flow:
- terminal 1
- terminal 3
Terminal flow:
terminals 4, 5 &10
terminals 6&7
terminal 8
Absorbed cap
Protection
Premitted temp:
operational
transport & storage
Emplacement
Mass (weight)
26
220V -15%..240V+10% or
100V -15%...110V+10%
50...60Hz +/- 6%
max.10A slow action
5A
5A (incl.capacity absorbed by motor
and pre-heater)
1A
2A
5A
3VA
IP40
-20...+60°C
-50...+60°C
any
controller 180g, socket 50g,
AGK accessories 12 g.
APPENDIX: COMPONENTS CHARACTERISTICS
Commands in the event of operational interference
Stray light/premature ignition
During pre-purge and/or pre-ignition there should be no flamesignal. If
there is a flame signal, eg from premature ignition due to a faulty sole-
noid, external light, short circuit in the photoresisto or wiring, malfunc-
tion in the flame signal amplifier, etc., at the end of pre-purge and
safety time the controller locks out the burner and stops the fuel flow
even during safety time.
Absence of flame
If there is no flame at the end of safety time the controller locks out
immediately.
Absence of flame during operation
If there is no flame during operation the controller cuts off the supply
of fuel and automatically initiates a fresh start-up programme: at the
end of t4 the start-up programme ends.
Whenever there is a safety stop, terminals 3-8 and 11 are de-energi-
sed in less than 1 second; at the same time a remote lockout signal is
transmitted through terminal 10. The controller can be reset after c.
50 seconds.