External Control Via Rs-485; Control System Pump Settings - Pentair WHISPERFLO VS Installation And User Manual

Variable speed pump
Table of Contents

Advertisement

External Control via RS-485

These pumps can be controlled from certain Pentair
control systems, via an RS-485 signal, when paired with
the RS-485 Automation Wiring Kit (P/N 356324z).
Note: IntelliConnect Control and Monitoring Systems
can NOT externally control this pump via RS-485.
The pump will need to be connected via digital
inputs. Refer to External Control via Digital Inputs on
page 6.
Note: If the pump is manually stopped using the
Start/Stop button, the pump will not run until the
Start/Stop button is pressed. If the Start/Stop
LED is illuminated, the pump is active and can be
controlled externally.
Only the GREEN and YELLOW wires will be used to
connect the pump to external controls via RS-485. See
Figure 4.
Automation System
COM Port
YELLOW
GREEN
Figure 4

Control System Pump Settings

Pump Type:
Variable Speed (VS)
Control systems with older firmware may require the
pump be designated "IntelliFlo VS".
This pump will not process control system commands
if designated a Variable Flow (VF) or Variable Speed/
Flow (VSF) pump.
Pump Address:
1 or 2
Ensure the assigned pump address matches the pump
address in the control system. Refer Setting the Clock
and Pump Address, page 8.
Refer to the control system manual for more information
on connecting and programming your pump.
Note: Only the GREEN and
YELLOW wires will be used. All
other wires should be cut off at the
cable sheath.
From
Pump
WHISPERFLO
VS and WHISPERFLO
®
TO WIRE FOR EXTERNAL CONTROL USING RS-485:
1. Route the communication cable from the Pump
Com Port (Figure 5) to the control system wiring
compartment.
2. Ensure the cable reaches all necessary terminals
and cut to the necessary length.
3. Strip 3/4 in. (19 mm) of sheathing from the
communication cable.
4. Strip 1/2 in. (13 mm) of sheathing from the 24 AWG
GREEN and YELLOW wires.
5. Cut back and terminate unused wires according to
local and national electrical codes.
6. Connect YELLOW and GREEN wires to the control
system as shown in Figure 4.
7. Program the pump's internal clock. Refer to Setting
the Clock and Pump Address on page 8.
8. Program SPEED 1 to a speed of 0 RPM and
duration of 24 hours. Refer to Programming Custom
Schedules on page 9.
9. Disable priming at the pump. Priming duration and
speeds will be controlled by the control system.
Note: If priming is not disabled at the pump,
priming will be continue to be controlled by the
pump. Refer to Priming on page 11.
10. Plug the communication cable into the Pump Com
Port (Figure 5).
11. Press the Start/Stop button to start the pump.
Pump
Com Port
VST Variable Speed Pump Installation and User's Guide
®
5