Eaton CH10GEN5030SN Instruction Booklet page 3

Corporation's family of manual transfer switches for residential and light commercial applications

Advertisement

Eaton Corporation's Family of Manual Transfer Switches
for Residential and Light Commercial Applications
Do Not Connect
the Utility or
Generator
Neutrals to the
Breaker if the
Generator is
Configured as a
Non-Separately
Derived System.
Leave These
Poles Empty.
Figure 3. Connection Locations for a Separately Derived System.
Connection for a Non-Separately Derived System:
2. For portable generators that are configured as a
Non- Separately Derived system.
a. Connect the two hot wires from the utility to the utility
breaker poles #1 and #2. Connect the utility neutral to the
utility neutral lug. See Figure 3 for clarification.
b. Connect the two hot wires from the generator to the gen-
erator breaker poles #1 and #2. Connect the generator
neutral to the neutral bar. See Figure 3 for clarification.
 dANger
FOr A NON-sepArATely derIved sysTem dO NOT CONNeCT The
UTIlITy Or geNerATOr NeUTrAls TO The UTIlITy breAker Or
geNerATOr breAker NeUTrAl pOle. These NeUTrAls mUsT be TIed
TOgeTher AT The NeUTrAl bAr. FAIlUre TO dO sO wIll leAd TO
eqUIpmeNT FAIlUre, FIre, Or pOssIble deATh dUe TO A FlOATINg
NeUTrAl CONdITION.
Instruction Booklet IB 70-8704
Effective January 2009
Utility Neutral
Utility Pole #1
Utility Pole #2
Generator Neutral
Generator Pole #1
Generator Pole #2
eaton corporation www.eaton.com