Atlas Copco G 2 Instruction Book page 19

Oil-injected rotary screw compressors
Hide thumbs Also See for G 2:
Table of Contents

Advertisement

Instruction book
Installation proposal
Ref.
1
2
3
4
(1)
(2)
(3)
(4)
(5)
Step
Action
1
Install the compressor on a solid, level floor suitable for taking the weight.
The recommended minimum distance between the top of the unit and the ceiling is 1.5 m (58.5
in).
The minimum distance between the wall and the back of the compressor must be 200 mm (7.8
in).
The pipes between a floor- mounted compressor and air receiver are hot.
2
Position of the compressed air outlet valve.
Close the valve.
Connect the air net to the valve.
2920 7170 31
Installation proposal, tank mounted units
Description/recommendation
Isolating switch, compressor
Isolating switch, dryer
Front panel, compressor
Dryer
Minimum 1.5 m
Space for maintenance, minimum 2 m
Single-phase dryer supply
Three-phase screw compressor supply
The power cable should be protected so that it complies with local codes
17