CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Table of Contents UCA/W/H/R Introduction Status Establishing Communication and Configuring Unload Status Modules Present Defrost Status Configuring System Type and Application Module Level Configuration Cool and Heat Setpoints Compressor Enable/Disable Free Cooling Setup Refrigeration Sensor and Alarms Remote Reset and Demand Limiting Setup Motorized Valve PID Settings...
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Introduction UCA/W/H/R This document outlines the quick start procedure for items that require configuration at initial system startup. Additional fine tuning may be required depending on the system’s application. This guide assumes the required software is installed on the CoolLogic Touch Controller and each of the Chiller Modules in the bank.
CoollogiC TouCh CONTROLS QUICK START GUIDE Establishing Communication and Models: Configuring Modules Present UCA/W/H/R Use this guide after the software is installed and all devices are properly addressed. Address the CoolLogic Touch Controller and Modules using the rotary dials on each control board. All control boards require a power cycle after setting the address.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Configuring System Type and Application UCA/W/H/R Select System Setup from the Home Screen. Chiller Module Type: Select the appropriate module type from the following options: UCW, UCH, UCR, UCA, UCA-UCF, UCA-HP, UCH-HP, UCH-HR. Chiller Control Type: Make your selection based on the bank application from the following options: Cool Mode, Heat Mode, or Heat Recovery.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Configuring System Type and Application UCA/W/H/R COOL AND HEAT SETPOINTS Disable Free Cool Lockout: If the outside ambient temperature (OAT) is less than the low ambient temperature trip point, Free Cooling is disabled if this option is selected.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Configuring System Type and Application UCA/W/H/R CONTROLLER CONFIGURATION Target Min Reset: The minimum setpoint for Remote Analog Target or BAS Target. Target Max Reset: The maximum setpoint for Remote Analog Target or BAS Target. Active Reset: The active remote setpoint.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: CoolLogic Touch Controller Level Configuration UCA/W/H/R From the menu. CoolLogic Touch Lockout Alarm Enter Passcode: The required Passcode to unlock the unit. MODULE SELECTOR FLOW SENSOR CONFIGURATION Select the module size for each module in the bank.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: CoolLogic Touch Controller Level Configuration UCA/W/H/R Use Low Diff Press Filter: Prevents flow from dropping The values in the example are the absolute immediately where the decrease in value is limited minimum for a UCH-style chiller, but can be by 1 psi every second.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: CoolLogic Touch Controller Level Configuration UCA/W/H/R PID SETUP START UP AND MODE CHANGE PID Configurations for both Heat Demand and Cool Demand. Start-up Time Delay: The time delay before the unit starts up. Recommended: Set PID tuning up to stage one Minimum mode Change Delay: The required delay compressor up/down every 5-8 minutes.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: CoolLogic Touch Controller Level Configuration UCA/W/H/R STANDBY MODULE SETUP (N+1) ENABLE PUMP This screen is used only when an ON/OFF pump is connected to BO3 on the CoolLogic Touch Controller. If Enable Pump is selected, the pump is enabled. Use N+1 Operation: Enable N+1 Operation.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Service Menu UCA/W/H/R CONFIGURE REFRIGERATION SENSORS DIAGNOSTICS MANUAL MODE The manual control for the system to test modules. Refrigeration Sensor Input Type: Choose between Honeywell, Carel(default) or Custom. If Custom is Current System Mode: Displays the current manual selected, the below values must be set.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Service Menu UCA/W/H/R RESET COMP RUNTIMES AND CYCLES ALARM LOCKOUT RESET Reset compressor runtimes and number of cycles for Configuration to clear module and CoolLogic Touch each compressor. Controller alarms. NOTE: Alarms are removed only if the cause of the CALIBRATE AND LOCK TEMPERATURES alarm is solved/removed.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Verifying Communications with Modules UCA/W/H/R Communication between the CoolLogic Touch Controller and Chiller Modules can be confirmed by entering the module’s Status Screen from the Home Screen. Selecting a module image displays the Module Status Screen for that module.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Status UCA/W/H/R Overall system status and commands. UNLOAD STATUS DEFROST STATUS Displays whether the modules or the compressors are in unload status. The bank is ready to start and run with the minimum configuration completed.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Module Level Configuration ( ) UCA/W/H/R Review the settings in each menu displayed below to confirm they are correct for the chiller application. Some of these settings are not available depending on the Module Unit Type selection in “CoolLogic Touch Controller Level Configuration”.
CoollogiC TouCh CONTROLS QUICK START GUIDE Module Level Configuration ( ) Models: UCA/W/H/R HEAT VALVE PID Low Suction Temperature: Sets the threshold below which the SUCTION TEMPERATURE ALARM is triggered Valve PID settings for Discharge Pressure Control for for the selected mode. air-source units.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Module Level Configuration ( ) UCA/W/H/R MODULE WATER TEMP LIMITS COMPRESSOR SETTINGS Decreasing the default values for Comp Minimum Run Time or Comp Minimum Off Time is not recommended. These values set the minimum ON and minimum OFF times for all compressors.
CoollogiC TouCh CONTROLS QUICK START GUIDE Module Level Configuration ( ) Models: UCA/W/H/R VFD/Digital Minimum Output Voltage: Variable Head Pressure Target: The fan control to discharge compressor minimum low voltage DC signal output. pressure in HEAT MODE. Initially, the fan controls to This option typically requires no adjustment.
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Module Level Configuration ( ) UCA/W/H/R DEFROST SETUP Liquid Injection Discharge Temp Enable: The minimum Discharge Temperature to enable Liquid Injection. Liquid Injection Discharge Temp Disable: The maximum Discharge Temperature to disable Liquid Injection. HOT GAS BYPASS CONFIGURATIONS Select Defrost Header Bypass Control: The Header Bypass is locked open in defrost if this is enabled with...
CoollogiC TouCh CONTROLS QUICK START GUIDE Module Level Configuration ( ) Models: UCA/W/H/R DEFROST LOAD LIMITING SETUP Valve PID setup for Suction Pressure control when in Defrost/Cool Mode for Air Source Units. w w w. c l i m a c o o l c o r p . c o m C r e a t e d : A u g u s t 3 0 , 2 0 2 3 PA G E : 2 1...
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Contact Information UCA/W/H/R For more information on any of the previous configuration menus, contact ClimaCool Technical Services at 405.815.3000 or www.climacoolcorp.com. PA G E : 2 2 C r e a t e d : A u g u s t 3 0 , 2 0 2 3 w w w.
Page 23
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Notes UCA/W/H/R w w w. c l i m a c o o l c o r p . c o m C r e a t e d : A u g u s t 3 0 , 2 0 2 3 PA G E : 2 3...
CoollogiC TouCh CONTROLS QUICK START GUIDE Models: Revision History UCA/W/H/R DATE ITEM ACTION 08/30/23 First Published • • 15 S. Virginia | Oklahoma City, OK 73106 *C97B0083N10* Phone: 405.815.3000 | Fax: 405.815.3052 www.climacoolcorp.com ClimaCool works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein.