Configuring System Type and Application

Select System Setup from the Home Screen.
Chiller Module Type: Select the appropriate module type from the following options: UCW, UCH, UCR, UCA,
UCA-UCF, UCA-HP, UCH-HP, UCH-HR.
Chiller Control Type: Make your selection based on the bank application from the following options: Cool
Mode, Heat Mode, or Heat Recovery.
Chiller Control Source: This selects the start/stop method the chiller bank uses.
Keypad – Enable using the keypad and the three-way switch in the LOCAL position.
Digital Input – Enable with dry contact closure of the Remote Chiller Enable terminals within the
CoolLogic Touch Control Panel and the three-way switch in the REMOTE position.
BAS – Enable via BACnet points and the three-way switch in the REMOTE position and the contact closure
at the CoolLogic Touch Control Panel terminals 42 and 43 of LVTB1.
Enable Chiller from Keypad: Enables chiller operation when the three-way switch is in the LOCAL position
(both must be ON for the unit to run).
Use High Ambient Temp Limit: When ON, this disables unit operation in high ambient temperature conditions
(default 115°f). For UCA/UCF banks only.
Disable Heating Below: The ambient temperature setpoint below which heating is disabled. This applies only
to air source units. For UCA Heat Pump banks only.
Disable Cooling Below: The ambient temperature setpoint below which cooling is disabled. This applies only
to air source units. For UCA/UCF banks only.
w w w. c l i m a c o o l c o r p . c o m
CoollogiC TouCh CONTROLS QUICK START GUIDE
C r e a t e d : A u g u s t 3 0 , 2 0 2 3
Models:
UCA/W/H/R
PA G E : 5