11 | Maintenance and troubleshooting
ð After shutdown, wait 5 minutes before opening the device.
11.6

Faults

11.6.1 Procedure
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device
has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
1. If a fault occurs, notify an appropriately authorized and qualified electrician or KACO new energy GmbH
Service.
2. The operator can only carry out actions marked with a B.
11.6.2 Rectifying the cause
B = Operator's responsibility ; E = The indicated work may only be carried out by an authorised electrician. ; K = The in-
dicated work may only be carried out by a service employee of KACO new energy GmbH!
Error
Possible cause
The LEDs do not light up Grid voltage not avail-
able
The device stops feeding
Defective circuit-break-
into the grid shortly
ers in the device
after being switched on,
even though there is
sunlight present.
Device is active but not
Grid-feed is interrupted
connected to the grid. A
due to a grid fault.
grid fault is displayed on
the status LED.
The grid fuse trips.
The grid fuse capacity is
too low.
The grid fuse trips.
Hardware damage on
the device.
The device is displaying
Faults in the grid.
an impossible daily peak
value.
Page 104
Explanation/remedy
› Check whether the DC and AC voltages are within the permit-
ted limits (see Technical Data)
› Notify KACO Service.
If the circuit-breakers are defective, the device will recognize
this during the self-test.
› Ensure that there is sufficient PV generator power.
› If the grid separation relay is defective, have it replaced by
KACO Service.
› Notify KACO Service.
Due to a grid fault (over/undervoltage, over/underfrequency),
the device stopped the feed-in process and disconnected from
the grid for safety reasons.
› Change the grid parameters within the permitted operating
limits (see the "Start-Up" section).
In case of a high level of solar radiation, the inverter exceeds its
rated current for a short period, depending on the PV gener-
ator.
Select the capacity of the device's backup fuse to be somewhat
higher than the maximum feed-in current (see the "Installa-
tion" section).
› Contact the grid operator if the grid failure continues to oc-
cur.
If the grid fuse trips immediately when the device goes into
feed-in mode (after the start-up period is complete), the
device's hardware is probably damaged.
› Contact KACO Service to test the hardware.
The device continues to operate as normal without losses to
the yield, even when an erroneous daily peak value is dis-
played. The value is reset overnight.
To reset the value immediately, switch the device off by dis-
connecting it from the grid and switching off the DC, then
switch it back on.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 105 TL3 KACO
blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet
Manual
150 TL3 KACO blueplanet 155 TL3 KACO blueplanet 165 TL3
By
E
E
K
E
E
E
E
E
E