Parameter
Parameter name
code
P01
Return Difference for
Target Water Temp.
P02
Reserved
P03
Reserved
P04
Cooling setting temp.
P05
Heating setting temp.
P06=TP4
The setting temp. that Exhaust
temp. too high protection
P07=TP0
Recover The setting temp. from the
too high exhaust temp.
P08
Compressor current protection
P09
Inlet water temp. compensation
P10
Reserved
P11
Defrosting cycle
P12
Defrosting enters the temp.
P13
Defrosting time
P14
Desrosting exit temperature
P15
Temp. difference between
defrosting environment and coil
pipe
P16
Ambient temperature of the
defrosting
P17
Expansion valve cycle
P18
Overheat Degree in Heating Mode
P19
Main valve set exhaust gas
P20
Main valve defrosting opening
degree
P21
Minimum opening degree of
the main valve
P22
Expansion valve mode
P23
Manual steps of the main valve
P24
Cooling opening degree of the
main valve
System parameter table
Adjust range
1℃~18℃
--
--
8℃~28℃
15℃~40℃
80℃~125℃
50℃~100℃
2A~50A
-5℃~15℃
--
20MIN~90MIN
-15℃~-1℃
2MIN~20MIN
1℃~40℃
0℃~15℃
0℃~20℃
20-90
-5-10
70-125
2-45
5-15
0 Manual /
1 Automatic
2-45
2-45
Default value
1℃
--
--
27℃
27℃
110℃
90℃
Reserved--Without
this function
0℃
--
40MIN
-3℃
5MIN
18℃
9℃
17℃
30
3
95
30
8
1
35
30
13