Tightening torque for installing cables to terminal block
0.8 to 1.2 N • m (7.1 to 10.6 lbf∙in)
6. 2.

Connecting the transmission cables

(1)
Turn the power off.
(2)
Make a hole in the center of the dust proof bushing with the Phillips
head screwdriver.
(3)
Pass the transmission cable and remote controller cable through
the hole of dust proof bushing and pull it into the network convertor.
(4)
Connect the transmission cable and remote controller cable to their
respective terminal block properly.
(5)
Securely tighten the cable tie and then confi rm that the cable will
not come out.
(6)
Once the wiring of the cables has been completed, mount the cover
to the network convertor. Use the screws (M4 × 6 mm) to mount the
cover.
(7)
Use the 4 screws (M4 × 20 mm) provided to mount the network con-
vertor to the behind ceiling, wall, fl oor or other suitable location.
Setting Method when connecting a group remote
controller
Remote controller cable
Transmission cable
Cable tie
Cable tie holder
Earth (Ground)
Cable
En-5
Dust proof
bushing
Cut
Cable tie
Terminal block
Cable tie holder
Setting method when connecting a single split indoor unit
Cut
Cable tie holder
Earth (Ground)
Cable
Tightening torque for installing cables to terminal block
7.

USING THE NETWORK CONVERTOR

The network convertor has 2 uses. Since the setting method is different
depending on how the network convertor is used, refer to the following
information to make the settings.
(1)
To connect a group
remote controller
(2)
To connect a single
split type indoor
unit
Earth
(Ground)
SETTING METHOD WHEN CONNECTING A GROUP RE-
MOTE CONTROLLER
8.

CIRCUIT BOARD SETTING

Set network convertor rotary switch SW110, SW111 and Dip switch
SW103, SW107, SW108, SW109.
[Rotary switch-SW110, SW111]
Convertor address settings
Set the convertor address in accordance with the following table for
each network convertor.
*
Be sure to set the convertor address different from the touch panel
controller address (refer to the setting manual for the touch panel
controller).
*
Each convertor address can be selected freely but the same address
Remote controller cables
Cut
Transmission cable
Cable tie
Cable tie
Cable tie holder
0.8 to 1.2 N • m (7.1 to 10.6 lbf∙in)
See items:
8.
CIRCUIT BOARD SETTING
9.
TURNING ON THE POWER
10. ERROR CODE
See items:
11. CONNECTION OF REMOTE CON-
TROLLER CABLE
12. CIRCUIT BOARD SETTING
13. TURNING ON THE POWER
14. SETTING CHECK MODE
15. ERROR CODE
Earth
(Ground)
Terminal block