Indoor Unit Status

Indoor Unit Status 1/3

Indoor Unit Status 2/3
Indoor Unit Status 3/3
Maintenance Menu
Press
"Cancel"
button
once.
Display
(3/3)
Maintenance Menu
1. Unit No.
2. FAN
3. FLAP
4. Speed
5. EV
6. MP
7. EH
8. Hu
9. TBF
1. FLOAT
2. T1/T2
1. Unit No.
2. Th1
3. Th2
4. Th3
5. Th4
6. Th5
7. Th6
Thermistor name varies depending on the connected indoor unit.
Basic screen
is displayed.
Press and hold
Press "Cancel"
"Cancel" button
button.
for 4 seconds or
more.
Service
settings menu
is displayed.
Press and hold
"Cancel" button
for 4 seconds
or more.
Select "Indoor Unit
Status" and press
"Menu/OK" button.
Maintenance
menu is
Press "Cancel" button.
displayed.
Press the " / " buttons.
Item 2
Select the Unit No. you want to check.
Fan tap
Airflow direction selected (swing, P0 to P4)
Fan speed (rpm)
Degree that electronic expansion valve is open (pulse)
Drain pump ON/OFF
Electric heater ON/OFF
Humidifier ON/OFF
Anti-freezing control ON/OFF
Displays the Unit No. selected.
Suction air thermistor
Heat exchanger liquid pipe thermistor
Heat exchanger gas thermistor
Discharge air thermistor
Details for Each Menu Item
Select the desired Unit
No. using the " /
(Up/Down)" buttons.
Item 2 is
The corresponding
displayed.
indoor status data will
be displayed.
Display
(1/3)
Display
(2/3)
Remarks