Daikin BRC1E73 Service Manual page 80

Navigation remote controller
Hide thumbs Also See for BRC1E73:
Table of Contents

Advertisement

Maintenance Menu List
2.3 Indoor Unit Status
2.4 Outdoor Unit Status 1. Unit No.
2.5 Forced Defrost
2.6 Error Display
2.7 Swap Unit No.
2.8 Addressed Sensor
71
Maintenance Menu
10.FLOAT
11.T1/T2
12.Unit No.
13.Th1
14.Th2
15.Th3
16.Th4
17.Th5
18.Th6
2. FAN step
3. COMP
4. EV1
5. SV1
6. Th1
7. Th2
8. Th3
9. Th4
10.Th5
11.Th6
1. Forced defrost ON
2. Forced defrost OFF
1. Display Error ON
2. Display Error OFF
3. Display Warning ON
4. Display Warning OFF
1. Current Unit No.
2. Transfer Unit No.
Unit No.: 0 - 15
Value
Code
Data
Thermistor name varies depending on the connected indoor or outdoor unit.
Item 2
Select the Unit No. you want to check.
Suction air thermistor
Heat exchanger liquid pipe thermistor
Heat exchanger gas pipe thermistor
Discharge air thermistor
Select the Unit No. you want to check.
Fan tap
Compressor power supply frequency (Hz)
Degree that electronic expansion valve is open
(pulse)
Solenoid valve ON/OFF
Enables the forced defrost operation.
Disables the forced defrost operation.
Displays the error on the screen.
Displays neither errors nor warnings.
Displays a warning on the screen if an error
occurs.
No warning is displayed.
A unit No. can be transferred to another.
Select the Unit No. you want to check.
00:
Remote controller thermistor (°F)
01:
Suction air thermistor (°F)
02:
Heat exchanger liquid pipe thermistor (°F)
03:
Heat exchanger gas pipe thermistor (°F)
04:
Indoor unit address No.
05:
Outdoor unit address No.
06:
Branch Selector unit address No.
07:
Zone control address No.
08:
Cooling/Heating batch address No.
09:
Demand/low-noise address No.
The corresponding data will be displayed, based
on the Unit No. and Code selected.
SiUS721424EB
Remarks
Maintenance Menu