10
|
Configuration
Benefit kWh power supply
Installer reference guide
210
NOTICE
ONLY disable water pipe freeze prevention if glycol is used. For more information on
freeze protection by glycol, see
4
freezing" [
98].
#
Code
[9.8.2]
[D-00]
[9.8.3]
[D-05]
"8.2.7 To protect the water circuit against
Description
Restriction: Only applicable if [9.8.4] is NOT set
to Smart Grid.
Allow heater: Which heaters are allowed to
operate during preferential kWh rate power
supply?
▪
0 No: None
▪
1 Only BSH: Booster heater only
▪
2 Only BUH: Backup heater only
▪
3 All: All heaters
See also below table (Allowed heaters during
preferential kWh rate power supply).
Setting 2 is only meaningful if the preferential
kWh rate power supply is of type 1 or the hydro
module is connected to a separate normal kWh
rate power supply (via X2M/5‑6) and the backup
heater is NOT connected to the preferential kWh
rate power supply.
Restriction: Only applicable if [9.8.4] is NOT set
to Smart Grid.
Allow pump:
▪
0 No: Pump is forced off
▪
1 Yes: No limitation
EPRA14~18D + ETVH16SU18+23E
Daikin Altherma 3 H HT F
4P644738-1D – 2023.10