Make sure to leave the first few threads at the end of the components free of tape.
8. Install the female (socket) quick-disconnect (A in the image in step 9) to the ½" NPT male-to-
female elbow (B in the image in step 9).
Use an adjustable wrench to tighten them.
9. Install the sub-assembly from step 8 (A+B in the image below) to the 125 mm particle filter
housing inlet (next to the red button, turning it so it is facing down; D in the image below).
Do not cross thread the particle filter housing and hand tighten the assembly.
B B
A A
10. Unscrew the particle filter bottom housing.
11. Install a new 5 um particle filter (P/N: 012-104287-XX).
12. Re-install the particle filter bottom housing.
13. Install the PT side of the ½" NPT-to-½" PT adapter (C in the image in step 9) to the chiller
return port.
Make sure to note the PT and NPT marking on the part and use adjustable wrenches to tighten
the adapter to the chiller.
14. Install the particle filter housing assembly (A+B+D in the image in step 9) to the NPT side of
the ½" NPT-to-½" PT adapter (C in the image in step 9) in the chiller return port.
Hand tighten the assembly and see the image below for the recommended orientation.
15. Remove the chiller reservoir cover.
16. Insert a tank particle filter (P/N:012-104286-XX).
17. Re-install the chiller reservoir cover.
Installing the SMC HRS-040 Chiller Instruction Sheet
020-103867-02 Rev. 1 (01-2024)
Copyright
©
2024 Christie Digital Systems USA, Inc. All rights reserved.
If printed, please recycle this document after use.
Installing and setting up the SMC HRS-040 chiller
C C
D D