Electrical Installation; About Electrical Compliance; Guidelines When Connecting The Electrical Wiring; Connections To The Outdoor Unit - Daikin EBLA16D V3 Installation Manual

Hide thumbs Also See for EBLA16D V3:
Table of Contents

Advertisement

Piping length (m)
<20
20~30
30~40
40~50
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator
which
can
professional.standbyme.daikin.eu.
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6

Electrical installation

DANGER: RISK OF ELECTROCUTION
WARNING
Rotating fan. Before powering ON the outdoor unit, make
sure that the discharge grille covers the fan as protection
against a rotating fan. See
grille" [ 4  17].
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length into the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1

About electrical compliance

Only for EBLA09~16D▲V3▼, EBLA09~16D▲3V3▼,
EDLA09~16D▲V3▼ and EDLA09~16D▲3V3▼
Equipment
complying
with
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Item
X1M
X2M
X3M
X4M
X5M
X9M
X10M
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620239-1B – 2022.05
Minimum insulation thickness
(mm)
19
32
40
50
be
reached
via
https://
"4.2.4  To install the discharge
EN/IEC  61000‑3‑12
(European/
Tightening torque (N•m)
2.45 ±10%
0.88 ±10%
0.88 ±10%
2.45 ±10%
0.88 ±10%
2.45 ±10%
0.88 ±10%
6.3

Connections to the outdoor unit

Item
Power supply (main)
See
"6.3.2 To connect the main power
supply" [ 4  23].
Power supply (backup
See
"6.3.3 To connect the backup heater
supply" [ 4  25].
heater)
power
(in case of outdoor unit
with integrated backup
heater)
Backup heater kit +
See
"6.3.4 External backup heater
kit" [ 4  26].
Bypass valve kit
(in case of external
backup heater kit)
User interface
See
"6.3.5 To connect the user
interface" [ 4  28].
Shut-off valve
See
"6.3.6 To connect the shut-off
valve" [ 4  30].
Electricity meters
See
"6.3.7 To connect the electricity
meters" [ 4  30].
Domestic hot water
See
"6.3.8 To connect the domestic hot
pump" [ 4  31].
pump
water
Alarm output
See
"6.3.9 To connect the alarm
output" [ 4  31].
Space cooling/heating
See
"6.3.10 To connect the space cooling/
operation control
heating ON/OFF
Changeover to
See
"6.3.11 To connect the changeover to
external heat source
external heat
control
Power consumption
See
"6.3.12 To connect the power
digital inputs
consumption digital
Safety thermostat
See
"6.3.13 To connect the safety
thermostat (normally closed
contact)" [ 4  33].
Smart Grid
See
"6.3.14 To connect a Smart
Grid" [ 4  33].
6 Electrical installation
Description
output" [ 4  31].
source" [ 4  32].
inputs" [ 4  32].
Installation manual
21