EBLA09~16D▲V3▼ (1N~), EDLA09~16D▲V3▼ (1N~), EBLA09~16D▲W1▼ (3N~) and EDLA09~16D▲W1▼ (3N~)
A
g
h
i
j
b
e
R1T
f
R4T
a
c
A
Hydro module
B
Compressor module
a
Water IN (screw connection, male, 1")
b
Water OUT (screw connection, male, 1")
c
Drain valve (water circuit)
d
Plate heat exchanger
e
Flow sensor
f
Expansion vessel
g
Safety valve
h
Manual air purge valve
i
Pump
j
Connection for optional flow switch
k
Liquid stop valve with service port
l
Gas stop valve with service port
m
Filter
n
Rectifier
o
Economiser
p
Heat sink
q
Distributor
r
Heat exchanger
s
Service port 5/16" flare
t
Accumulator
u
Muffler
EBLA09~16D + EDLA09~16D
Daikin Altherma 3 M
4P620239-1B – 2022.05
m
B1PW
u
S1NPH
l
d
k
R3T
B
Y1S
Y3E
u
*
S1PH
M1C
t
1N~
3N~
*
*
B1PW
Space heating water pressure sensor
M1C
Compressor
S1PH
High pressure switch
S1PL
Low pressure switch
S1NPH
Pressure sensor
Y1E
Electronic expansion valve (main)
Y3E
Electronic expansion valve (injection)
Y1S
Solenoid valve (4-way valve)
Thermistors (hydro module):
R1T
Outlet water heat exchanger
R3T
Refrigerant liquid side
R4T
Inlet water
Thermistors (compressor module):
R1T
Outdoor air
R2T
Compressor discharge
R3T
Compressor suction
R4T
Air heat exchanger
R5T
Air heat exchanger, middle
Refrigerant flow:
Heating
Cooling
Connections:
Screw connection
Flare connection
Quick coupling
Brazed connection
11 Technical data
m
n
**
Y1E
p
o
R5T
q
1N~
3N~
**
**
3D128954A
Installation manual
r
s
49