Step 2: Make two Φ3.5 cutouts in the middle positions on the
cover, as shown below, according to the outlines of the locking
ON/OFF button when placed against the cover.
Figure 2. Step 2
Step 3. Secure the button lock to the cover with M3×12 screws
and M3 nut.
Nut M3
Figure 3. Step 3
Step 4: Put the cover back.
N
otes:
The padlock is prepared by customers themselves.
M3×12
IZM6 Series Air Circuit Breaker Instruction Manual MN013019EN March 2023 www.eaton.com.cn
Section 5: IZM61/65/67 accessory installation
IZM65/67 latch check switch (LCS)
(1) Only qualified electrical personnel should be permitted to
work on the equipment.
(2) Always de-energize primary and secondary circuits if a circuit
breaker cannot be removed to a safe work location.
(3) Drawout circuit breakers should be levered (racked) out to the
disconnect position.
(4) All circuit breakers should be switched to the off position and
mechanism springs discharged.
Failure to follow these steps for all procedures described in this
instruction leafl et could result in death, bodily injury, or property
damage.
Section 1: General information
The circuit breaker sends out a signal when ready to close.
Tools required
• Phillips screwdriver
• 10mm socket or 10mm wrench
Kit parts identification
• LCS (1)
• Screws M4×10 (2)
Section 2: Installing the LCS
Follow below steps for installation:
Step 1: Remove the mounting screws from the circuit breaker
panel with the Phillips screwdriver. Pull down the charging handle
(by an approx. 45° angle) to remove the cover.
Figure 1. Step 1
WARNING
Screw
37