Section 2: Installing the position cell switch
Follow below steps for installation:
Step 1: First, lever out the basic device to the Disconnected posi-
tion for removal.
Step 2: Place the position cell switch onto the left side panel of
the cassette, and secure it with M4×8 screws (the wiring terminal
of the cell switch needs to be removed first, and put back after
mounting). Attach the label above the measuring position after
mounting.
Tapping screw 4.2×13
Figure 1. Step 2: Outer side view
Figure 2. Step 2: Inner side view
W6
DISCONNECT
W4
TEST
W2
CONNECT
Figure 3. Step 2: Label
W5
W3
W1
16A 380VAC
250VAC
0.3A 250VDC
IZM6 Series Air Circuit Breaker Instruction Manual MN013019EN March 2023 www.eaton.com.cn
Section 5: IZM61/65/67 accessory installation
Step 3: Remove the basic device cover, then the left bracket with
the Allen wrench. Mount the slider (with the M3×10 screw, Φ3
elastic washer and M3 nuts). Then, place the bracket back into
the circuit breaker's basic device.
Left support
Figure 4. Step 3
Nut M3
Gasket Φ3
Figure 5. Step 3
Step 4: Remove the small square groove on the left side of the
cover with the knife, as indicated below, then put the cover back.
Figure 6. Step 4
Step 5: Finally, put the basic device into the cassette, and mea-
sure whether the corresponding switch at the three positions can
be properly switched on.