Eaton IZM6 Series Instruction Manual page 11

Air circuit breaker
Hide thumbs Also See for IZM6 Series:
Table of Contents

Advertisement

Internal auxiliary contact
• IZM61/65/67
GB9074.8 M4X10
IZM61
External auxiliary contact
For IZM61/65/67 series circuit breakers, external auxiliary con-
tacts are needed when there are more than 4 open and 4 closed
auxil-iary contacts.
External auxiliary contact terminal numbers
62 64 65 67 68 70 71 73 74 76 77 79 80 82 83 85 86 88 89 91
63
66
69
72
Rated operating
voltage U
Auxiliary contact
AC400
AC230
DC220
DC110
Undervoltage and Novoltage releases
GB9074.8 M4X16
IZM65/67
75
78
81
84
87
90
Conventional
Rated control
thermal
(V)
capacity
current I
e
800VA
6
300W
IZM6 Series Air Circuit Breaker Instruction Manual MN013019EN March 2023 www.eaton.com.cn
Undervoltage
• IZM61/65/67
GB9074.8 M4x10
IZM61
In areas prone to thunderstorms or in power grids with unstable
power supply voltage, it is recommended to use under voltage
trip units with time delay functions, to prevent the circuit breaker
from tripping due to short-time voltage drop. The delay time can
be selected usually from 0.3s,0.5s,0.7s,1s, 3s, 5s, to 10s by users.
For special requirements on the delay time, please contact Eaton.
Rated operating voltage U
Actuating voltage (V)
Reliable closing voltage (V)
Reliable no-closing voltage (V)
Pickup power
IZM61
IZM65/67
Maintaining
IZM61
power
IZM65/67
(A)
th
Section 4: Accessory
GB29.2 2×M4×62
IZM65/67
AC24/
AC48/
AC110/
(V)
DC24
DC48
DC110
e
(0.35-0.7) U
e
(0.85-1.1) U
e
≤0.35 U
e
263W
331W
773W
228W
269W
220W
2.2W
2.62W
2.8W
5.7W
6.2W
8.6W
AC230/
DC220
AC400
570W
408W
456W
508W
4W
3.5W
4.2W
6.6W
11