Electric Heater Kit Selection Table - Friedrich Breeze Series Service Manual

Mini split ducted heat pumps
Table of Contents

Advertisement

Electric Heater Kit Selection Table

Electric
Air
Heat Kit
Handler
Model
Model
AUX5KW
24k
AUX7KW
AUX10KW
AUX5KW
36k
AUX7KW
AUX10KW
AUX15KW
AUX5KW
48K/60K
AUX7KW
AUX10KW
AUX15KW
AUX20KW
NOTES:
When optional electric heater kit is installed, obtain power for AHU from load side of L1 and L2 of electric heater kit.
It is recommended that the electric heater kit should be installed in cold climate regions or when long piping is used.
Properly size the auxiliary heater per the table above.
Ampacities for MCA and Fuse/breaker include the blower motor.
Heat pump systems require a specified airflow. Each ton of cooling requires between 350 and 450 cubic feet of air per minute
(CFM).
14
SPECIFICATIONS
Electric
MIN. Circuit Ampacity
Heat (kW)
230VAC
208VAC
5
28.3
25.9
7.5
40.7
37.2
10
53.2
48.5
5
29.8
27.4
7.5
42.2
38.7
10
54.7
49.9
15
42.2+36.9 38.6+33.8
5
31.8
29.4
7.5
44.8
40.7
10
56.7
51.9
15
44.8+36.9
40.7+33.8
20
56.7+49.9
51.9+45.2
MAX. Fuse or
Breaker (HACR)
Ampacity
230VAC
208VAC
30
30
45
40
60
50
30
30
45
50
60
50
45+40
40+35
35
30
45
45
60
55
50+40
50+35
60+50
60+50
O = Fan Speed tap may be used
X= Fan speed tap may not be used
See Blower Data(Indoor Units)
Figure 203
Fan Speed Tap
2
3
4
O
O
O
X
O
O
X
X
O
O
O
O
X
O
O
X
X
O
X
X
X
0
O
O
X
O
O
X
X
O
X
X
O
X
X
X
5
O
O
O
O
O
O
0
O
O
O
O
O