ABB ACS580 Series Hardware Manual page 334

General purpose drives
Hide thumbs Also See for ACS580 Series:
Table of Contents

Advertisement

334 Technical data
Frame
Cable
size
entries
Per
1)
Ø
cable
type
pcs
in
3-phase U 1 = 525...600 V, P n at U n = 575 V, 60 Hz
R2
1
1.38
R3
1
1.73
R5
1
2.01
R7
1
2.99
R8
2
2.44
R9
2
2.44
1) Diameter of the cable entry plate hole.
2) Note: Minimum wire size does not necessarily have enough current capability for full load.Make sure
the installation complies with local laws and regulations.
3) Either cable lug, not provided (R5) or cable clamp (R6...R9) is used for grounding.
For IP66 (UL Type 4X) with disconnect option, input cable entries, maximum wire
sizes (per phase), terminal screw sizes and tightening torques (T) are given below.
Frame
Cable entries
size
Per
Ø
cable
type
pcs
3-phase U 1 = 200...240 V, P n at U n = 208/230 V, 60 Hz
R1
1
0.87
R2
1
0.87
R3
1
1.12
3-phase U 1 = 440...480 V, P n at U n = 480 V, 60 Hz
R1
1
0.87
R2
1
0.87
R3
1
1.12
3-phase U 1 = 525...600 V, P n at U n = 575 V, 60 Hz
L1, L2, L3, T1/U, T2/V, T3/W terminals
Wire range (stranded/solid)
Min
AWG
20
20
6
3/0
2×1/0
2×300 MCM
2×3/0
2×500 MCM
2T1, 4T2, 6T3 Terminals
1)
Min. wire size
(solid/stran-
2)
ded)
in
AWG
3)
14
3)
14
4)
14
3)
14
3)
14
4)
14
2)
T
Wire range (stranded/sol-
Max
AWG
lbf·ft
6
1.1
2
2.6
1/0
11.1
500 MCM
29.5
29.5
51.6
Max. wire size
(solid/stran-
ded)
AWG
4
4
4
4
4
4
Grounding terminals
id)
Min
Max
AWG
AWG
18
6
18
2
3)
3)
3)
350 MCM
3)
2×350 MCM
3)
2×350 MCM
Grounding terminals
T
Max. wire
size
lbf·ft
AWG
4.6
6
4.6
6
4.6
2
4.6
6
4.6
6
4.6
2
T
lbf·ft
1.1
1.1
1.6
7.2
7.2
7.2
T
lbf·ft
1.1
1.1
1.1
1.1
1.1
1.1

Advertisement