User Manual
Step 2 Set the following parameters.
Parameter
Initial Status
Inverter
Action
Triggered by DI
Recovery
Action
Delay
Time After DI
Recovery
Inverter
Action
Triggered by DI
Action
Action
Delay
Time After DI
Action
Purpose
If Inverter Action Triggered by DI Action is set to Boot, the opposite action is
Shutdown.
If Inverter Action Triggered by DI Action is set to Shutdown, the opposite ac-
tion is Boot.
If Inverter Action Triggered by DI Action is set to Not Operated, no instruction
is sent to the inverter.
Description
The status of the DI port during normal operation.
The inverter status can be restored to normal by the following
methods.
•
Manual control: The user manually restore the inverter status to
normal.
•
Automatic control: The Logger1000 issues an instruction to restore
the inverter status to normal.
It refers to the interval between Logger1000 receiving the DI status re-
covery signal and issuing the instruction to restore the inverter status
in the Automatic control mode. If there is no other change in the DI
signal within this period, the action opposite to that set in Inverter Ac-
tion Triggered by DI Action is executed.
This parameter does not need to be set in Manual control mode.
The DI port status changes and the Logger1000 issues instructions to
the inverter.
•
Not Operated: Do not send instructions to the inverter.
•
Boot: Send an instruction to power on the inverter.
•
Shutdown: Send an instruction to shut down the inverter.
It refers to the interval between Logger1000 receiving the DI status
change signal and issuing the instruction to change the inverter status.
If there is no other change in the DI signal within this period, the action
set in Inverter Action Triggered by DI Action is executed.
It notes the purposes of DI ports.
7 WEB Interface
65
Need help?
Do you have a question about the Logger1000A and is the answer not in the manual?