SUN2000-(125KTL-M5, 200KTL-H4, 250KTL-H0,
286KTL-H0)
User Manual
No.
Category
9
10
11
12
Soft start time
13
Shutdown
gradient
14
Auto shutdown
settings
Issue 04 (2023-09-22)
Parameter
Description
Reactive power
Specifies the protection
mode when
threshold of the reactive
communication
power after communication is
fails
interrupted, including Q/S
and power factor.
Reactive power
Specifies the Q/S threshold of
threshold when
the reactive power (%)
communication
fails (%)
Reactive power
Specifies the power factor
threshold when
threshold of the reactive
communication
power (PF)
fails
Soft start time
Specifies the duration
(s)
required for gradual power
increase when the device
starts.
Shutdown
Specifies the power change
gradient (%/s)
rate when the device shuts
down.
Shutdown at 0%
If this parameter is set to
power limit
Enable, the device shuts
down after receiving the 0%
power limit command. If this
parameter is set to Disable,
the device does not shut
down after receiving the 0%
power limit command.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Remarks
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and
Reactive power
threshold when
communication
fails is set to Q/S.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and
Reactive power
threshold when
communication
fails is set to Power
factor.
-
-
-
90