Huawei SUN2000-125KTL-M5 User Manual page 92

Table of Contents

Advertisement

SUN2000-(125KTL-M5, 200KTL-H4, 250KTL-H0,
286KTL-H0)
User Manual
No.
Parameter
7
Grid connection time
after power grid
recovery (s)
8
Quick startup for
short-time grid
disconnection
9
Duration for
determining short-
time grid
disconnection (ms)
10
Soft start time after
grid failure (s)
11
Maximum voltage of
grid-tied startup (V)
12
Minimum voltage of
grid-tied startup (V)
13
Maximum frequency
of grid-tied startup
(Hz)
14
Minimum frequency of
grid-tied startup (Hz)
15
Grid reconnection
voltage upper limit (V)
16
Grid reconnection
voltage lower limit (V)
17
Grid reconnection
frequency upper limit
(Hz)
18
Grid reconnection
frequency lower limit
(Hz)
19
Delay time for
connecting
automatically to the
network
Issue 04 (2023-09-22)
Description
Specifies the time after which the device begins restarting
following recovery of the power grid.
Specifies whether to allow the device to quickly start after the
power grid recovers from a short-time failure.
In order to comply with the standards of certain countries and
regions, the device should not disconnect from the power grid
in cases where the grid experiences a short-time failure. After
the fault is rectified, the output power of the device must be
quickly restored.
Specifies the time required for gradual power increase when the
device restarts following power grid recovery.
According to the standards of certain countries and regions,
initial grid connection is not allowed when the grid voltage is
higher than the maximum voltage for grid connection.
According to the standards of certain countries and regions,
initial grid connection is not allowed when the grid voltage is
below the minimum voltage for grid connection.
According to the standards of certain countries and regions,
initial grid connection is not allowed when the grid frequency is
higher than the maximum frequency for grid connection.
According to the standards of certain countries and regions,
initial grid connection is not allowed when the grid frequency is
below the minimum frequency for grid connection.
According to the standards of certain countries and regions,
grid reconnection is not allowed when the grid voltage is higher
than the maximum grid voltage for grid reconnection.
According to the standards of certain countries and regions,
grid reconnection is not allowed when the grid voltage is below
the minimum grid voltage for grid reconnection.
According to the standards of certain countries and regions,
grid reconnection is not allowed when the grid frequency is
higher than the maximum grid frequency for grid reconnection.
According to the standards of certain countries and regions,
grid reconnection is not allowed when the grid frequency is
below the minimum grid frequency for grid reconnection.
Specifies the time after which the device begins restarting
following the power grid recovery.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
85

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sun2000-200ktlh4Sun2000-250ktl-h0Sun2000-286ktl-h0

Table of Contents