SUN2000-(125KTL-M5, 200KTL-H4, 250KTL-H0,
286KTL-H0)
User Manual
Port
Pin
RS485-2
1
3
-
5
RS485-1
7
Note [1]: In the RS485 communication networking, it is recommended that fewer than 30
inverters be cascaded to each COM port of the SmartLogger. The RS485 communication distance
between the inverters and the SmartLogger cannot exceed 1000 m.
Procedure
Step 1 Connect communications cables to the connector, prepare M4 OT or DT terminals,
and crimp ground cables for the shield layers.
Figure 5-24 Preparing RS485 communications cables
(1) Shield layer
Step 2 Connect the connector to the COM port, secure the shield layers to the ground
point of the communications cables, and bind the cables.
Issue 04 (2023-09-22)
Definition
RS485A IN, RS485
differential signal+
RS485B IN, RS485
differential signal–
-
-
Copyright © Huawei Technologies Co., Ltd.
Pin
Definition
2
RS485A OUT,
RS485 differential
signal+
4
RS485B OUT,
RS485 differential
signal–
6
-
8
-
5 Connecting Cables
Description
Used for cascading
inverters or
connecting to a
device such as the
[1]
SmartLogger.
Reserved
Reserved
52