Huawei SUN2000-125KTL-M5 User Manual page 96

Table of Contents

Advertisement

SUN2000-(125KTL-M5, 200KTL-H4, 250KTL-H0,
286KTL-H0)
User Manual
No.
Category
4
5
6
7
8
Issue 04 (2023-09-22)
Parameter
Description
Communication
If this parameter is set to
disconnection
Enable, the device performs
fail-safe
protection according to the
set power when
communication between the
device and the SmartLogger
is interrupted for a period
longer than Communication
disconnection detection
time.
Communication
Specifies the fail-safe
disconnection
detection time for
detection time
disconnection between the
(s)
device and the SmartLogger
or Smart Dongle.
Active power
Specifies the protection
mode when
threshold of the active power
communication
after communication is
fails
interrupted. The value can be
a percentage or a fixed value.
Active power
Specifies the active power
threshold when
threshold in percentage.
communication
fails (%)
Active power
Specifies the active power
threshold when
threshold as a fixed value.
communication
fails (kW)
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Remarks
-
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and Active
power threshold
when
communication
fails is set to a
percentage.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and Active
power threshold
when
communication
fails is set to a fixed
value.
89

Advertisement